background image

 

Operation

GENO

-Multi BS 

 
 

  

 

Order no. 004 523 950-gb   Edited by: KONS-rjau-mrie G:\BA-523950-GB_KD-F.DOC 

-CONFIDENTIAL- 

F-7

 

2.1.2   Programming parameters

 

Key functions with parameter programming – requirement: Basic 
display of irradiance [W/m²]. 

 

Key Display 

 

 

Press the key > 1 sec.: Access to parameter programming  
(opt. temperature flushing system). 

 

Open the parameter for reprogramming – the value begins to flash. 

 

Save the parameter – the value stops flashing. 

 

 

Reduce the opened parameter (while value flashes). 

 

Return to the previous parameter. 

 

 

Increase the opened parameter (while value flashes). 

 

Return to the next parameter. 

 

 

 

Close the opened parameter without saving – the old set value is main-
tained. 

 

Jump back to the basic display of irradiance. 

 

 

 

Open the display of the code query "Code C.000" >> access to code-
protected programming levels. 

 

2.2   User programming level

The limit value for the optional temperature flushing system is 
saved in the user programming level: 

 

Setting range 10 … 60 °C / factory setting 38 °C 

 

When the limit value is reached the rinsing solenoid valve opens 
and the display shows Er 3, the zero-potential contact ALARM 
opens. 

 

The rinsing solenoid valve remains open until the water has 
cooled down by 2 °C. 

 

The malfunction can be manually acknowledged and rinsing is 
not stopped by this. 

+

 

+

 

Summary of Contents for GENO-UV 120 S

Page 1: ...section consists of a lose collection of sheets that should according to the respective chapter and page number refer to header and footer be attached to the corresponding chapters of the standard ope...

Page 2: ......

Page 3: ...device For determination of the SAK254 please send a water sample of at least one liter to our internal lab The testing of the UV systems for the disinfection of drinking water is carried out at a des...

Page 4: ...tested by the DVGW is maintained Table E 1 Indicator points certified by the DVGW System SAK254 10 50 100 max flow min irradiance m 1 m h W m GENO UV 60 S 2 7 94 0 74 1 55 0 3 3 11 5 GENO UV 120 S 8 0...

Page 5: ...rating panels and display 2 2 Operation programming level 2 3 Installer level code 290 2 4 Error memory code 245 2 5 Displaying the software version code 999 2 6 Customer service level code 302 2 7 Re...

Page 6: ...level Key Display Unit LED Basic display of irradiance XX XX W m X Operating duration XXXX Days X Switch on processes XXXX X Time until service is due XXXd Days Back to basic display of irradiance or...

Page 7: ...d parameter while value flashes Return to the next parameter Close the opened parameter without saving the old set value is main tained Jump back to the basic display of irradiance Open the display of...

Page 8: ...or the menu to be edited The code for the level required here is 290 2 Press key to count upwards until C 290 appears in the display OR Press key to count downwards until C 290 appears in the display...

Page 9: ...hould be reset so that they display the code for the menu to be edited The code for the level required here is 245 2 Press key to count upwards until C 245 appears in the display OR Press key to count...

Page 10: ...l code 302 Index Parameter Unit Factory setting Setting range Note 0 Calibration of UV sensor W m Current irradiance 0 45 0 see chapter H 2 1 1 Irradiance limit value W m According to currently set da...

Page 11: ...ooting This is what you observe This is the cause This is what to do Er 1 and UV lamp light up Irradiance limit value System is dirty inside Service life 730 days or 18 000 h of UV lamp has been excee...

Page 12: ...20 mA interrupted UV sensor connection plug in serted correctly Optional USB data recording device wired incorrectly Er 6 or Er 7 Wire fracture or short circuit of the temperature sensor only when the...

Page 13: ...Check seals and replace if necessary Check functioning of the safety device Check functioning of a possibly existing rinsing valve Rinse UV disinfection system if required Clean protective pipes if ne...

Page 14: ...afety device that might be installed If the system is switched off the safety device must close check the water flow Check the functioning of a temperature flushing system that might be installed Dip...

Page 15: ...ation log On the GENO Multi BS control unit change to calibration level code 302 and open the parameter 0 XX X with the key P for editing 0 XX X flashes Remove the system sensor insert the reference s...

Page 16: ...Edited by KONS mhug mrie G BA 523950 GB_KD H DOC H 8 3 Resetting the operating hours and the switch on counter After replacing the lamp the operating duration and switch on counter should be reset Rep...