Maintenance and Care - Customer Service Section 

GENO

®

 UV systems with GENO

®

-Multi BS

 

 

 
 

-CONFIDENTIAL- 

Order no

. 024 523 950-gb   Edited by: KONS-mhug-mrie G:\BA-523950-GB_KD-G.DOC 

G-6 

Continuation Table 1:

 

 

 

This is what you observe

 

This is the cause

 

This is what to do

 

Er 4 

Excess temperature (only when the 
optional temperature flushing sys-
tem is installed). 

 

Water temperature > 40 °C. 

 

Set rinsing temperature lower. 

 

Check the functionality of the 
rinsing valve. 

Er 5 or display EEEE. 

Wire fracture of UV sensor or sen-
sor signal 4-20 mA interrupted. 

 

UV sensor connection plug in-
serted correctly? 

 

Optional USB data recording 
device wired incorrectly? 

Er 6 or Er 7 

Wire fracture or short circuit of the 
temperature sensor (only when the 
optional temperature flushing sys-
tem is installed). 

 

Temperature sensor = PT100, 
meaning sensor resistance is ap-
prox. 125 ohms at 25 °C. 

Display and all LEDs dark. 

Mains switch is switched off. 
Power supply is interrupted (inte-
grated fuse, supply line). 

 

Switch on mains switch. 

 

Replace the glass tube microfuse 
T 2 A (see chapter D). For this 
the fuse terminals are folded out 
downwards and then to the 
right. 

"Operating duration" LED flashes. 

Service interval has elapsed. 

Carry out maintenance and restart 
the service interval. 

 

Summary of Contents for GENO-UV 120 S

Page 1: ...section consists of a lose collection of sheets that should according to the respective chapter and page number refer to header and footer be attached to the corresponding chapters of the standard ope...

Page 2: ......

Page 3: ...device For determination of the SAK254 please send a water sample of at least one liter to our internal lab The testing of the UV systems for the disinfection of drinking water is carried out at a des...

Page 4: ...tested by the DVGW is maintained Table E 1 Indicator points certified by the DVGW System SAK254 10 50 100 max flow min irradiance m 1 m h W m GENO UV 60 S 2 7 94 0 74 1 55 0 3 3 11 5 GENO UV 120 S 8 0...

Page 5: ...rating panels and display 2 2 Operation programming level 2 3 Installer level code 290 2 4 Error memory code 245 2 5 Displaying the software version code 999 2 6 Customer service level code 302 2 7 Re...

Page 6: ...level Key Display Unit LED Basic display of irradiance XX XX W m X Operating duration XXXX Days X Switch on processes XXXX X Time until service is due XXXd Days Back to basic display of irradiance or...

Page 7: ...d parameter while value flashes Return to the next parameter Close the opened parameter without saving the old set value is main tained Jump back to the basic display of irradiance Open the display of...

Page 8: ...or the menu to be edited The code for the level required here is 290 2 Press key to count upwards until C 290 appears in the display OR Press key to count downwards until C 290 appears in the display...

Page 9: ...hould be reset so that they display the code for the menu to be edited The code for the level required here is 245 2 Press key to count upwards until C 245 appears in the display OR Press key to count...

Page 10: ...l code 302 Index Parameter Unit Factory setting Setting range Note 0 Calibration of UV sensor W m Current irradiance 0 45 0 see chapter H 2 1 1 Irradiance limit value W m According to currently set da...

Page 11: ...ooting This is what you observe This is the cause This is what to do Er 1 and UV lamp light up Irradiance limit value System is dirty inside Service life 730 days or 18 000 h of UV lamp has been excee...

Page 12: ...20 mA interrupted UV sensor connection plug in serted correctly Optional USB data recording device wired incorrectly Er 6 or Er 7 Wire fracture or short circuit of the temperature sensor only when the...

Page 13: ...Check seals and replace if necessary Check functioning of the safety device Check functioning of a possibly existing rinsing valve Rinse UV disinfection system if required Clean protective pipes if ne...

Page 14: ...afety device that might be installed If the system is switched off the safety device must close check the water flow Check the functioning of a temperature flushing system that might be installed Dip...

Page 15: ...ation log On the GENO Multi BS control unit change to calibration level code 302 and open the parameter 0 XX X with the key P for editing 0 XX X flashes Remove the system sensor insert the reference s...

Page 16: ...Edited by KONS mhug mrie G BA 523950 GB_KD H DOC H 8 3 Resetting the operating hours and the switch on counter After replacing the lamp the operating duration and switch on counter should be reset Rep...

Reviews: