Operation
GENO
-Multi BS
-CONFIDENTIAL-
Order no
. 004 523 950-gb Edited by: KONS-rjau-mrie G:\BA-523950-GB_KD-F.DOC
F-8
2.3 Installer level
Code 290
Note:
The parameters specified below should only be modified by
trained experts as incorrect values may lead to malfunctions or
insufficient disinfected drinking water.
Requirement: The control unit shows the basic display of irradi-
ance.
1.
Press keys + at the same time until the display
changes.
The installer level is active. The required menu must be selected
first. The numbers (000) flash.
These should be reset so that they
display the code for the menu to be edited.
The code for the level
required here is 290.
2.
Press key to count upwards until C.290 appears in the
display.
OR
Press key to count downwards until C.290 appears in
the display.
Hold down keys and so that the numbers run faster; press
the keys for fine adjustment.
3.
Press key to accept code 290.
Note:
In contrast to the Info level, it is possible to move backwards
and forwards between the individual parameters in the installer
level using keys and .
Index Parameter,
Unit
Factory
setting
Setting
range
Note
0
System type
0 60
60/120/
200/201
60 = UV60
120 = UV120
200 = UV200 with SAK
254
= 2.7
201 = UV200 with SAK
254
= 5.1
1
Option temperature flush-
ing system
1 0
0 … 1
0 = deactivated
1 = activated
2
Service interval [days]
2 0
0 … 730
Restart the service interval by
reprogramming