No non-return valve or flap should ever be fitted between the safety valve or safety unit
and the tank.
5.3.2. Safety valves:
The safety valves are fitted to the tank inlet using a T (see diagram below).
SAFETY UNIT
SAFETY VALVE
On cold water inlet only
On tank inlet
1 single G 1¨ unit
1¼¨ kit with 2 G 1¨ units
Valve diameter ≥
tank connector diameter
Safety valve/non-return flap/valve
A non-return flap preceded by a valve must be fitted to the cold water inlet if the tank is
equipped with a safety valve. To avoid scaling of these components, operate the safety unit
at least once a month by moving its controls to various positions.
6. ELECTRIC ELEMENTS
These estimated heating times are given for storage at 60°C and cold water at 10°C
.
On CORSI Shielded option
It is possible to add 4,5 to 20 kW shielded resistors, according to the following recommended
combinations
.
300 L
500 L
750 L 1000 L 1500 L
Heated volume
192
358
555
798
1100
4,5 kW
2:30
10 kW
2:00
3:15
4:45
15 kW
3:00
4:15
20 kW
3:15
Three-phase 230 / 400 V wiring is possible. See the document supplied with the resistor.
7. COMMISSIONING
• Fill the device
- Open a hot water tank in the distribution system,
- Open the cold water tap on the safety unit, ensuring that the unit's drainage valve is
closed,
- After drawing from the hot water taps with no noise in the pipes, close the taps: your
equipment is full.
Summary of Contents for CORSI
Page 2: ......
Page 27: ...01 02 2019 CORSI 27 36 ANNEXE A APPENDIX A BIJLAGE A ...
Page 31: ...01 02 2019 CORSI 31 36 ANNEXE B APPENDIX B BIJLAGE B ...
Page 33: ...01 02 2019 CORSI 33 36 ANNEXE C APPENDIX C BIJLAGE C ...
Page 35: ...01 02 2019 CORSI 35 36 DATES DATA TYPE TAMPON HOOD BUFFER ENTRETIENS UPKEEP ONDERHOUD ...