E30.0.0X.6C-11
Operating Manual GRA0420VO / GRA010VO
page 11 of 12
8 Error codes:
When detecting an operating state which is not permissible, the device will display an error code.
The following error codes are defined:
Err.1:
Exceeding of the measuring range
Indicates that the valid measuring range of the device has been exceeded.
Possible causes:
- Input signal to high
- Sensor shorted (0(4)-20mA)
Remedies:
- The error-message will be reset if the input signal is within the limits.
- check transmitter and device configuration (e.g. input signal).
Err.2:
Values below the measuring range
Indicates that the values are below the valid measuring range of the device.
Possible causes:
- Input signal is to low or negative
- Current below 4mA
- Sensor broken (4-20mA)
Remedies:
- The error-message will be reset if the input signal is within the limits.
- check transmitter and device configuration (e.g. input signal).
Err.3:
Display range has been exceeded
Indicates that the valid display range (9999 digit) of the device has been exceeded.
Possible causes:
- Incorrect scale
Remedies:
- The error-message will be reset if the display value is below 9999.
Err.4:
Values below display range
Indicates that display value is below the valid display range of the device (-1999 digit).
Possible causes:
- Incorrect scale
Remedies:
- The error-message will be reset if the display value is above -1999.
Err.7:
System-error
The device features an integrated self-diagnostic-function which checks essential parts of the de-
vice permanently. When detecting a failure, error-message Err.7 will be displayed.
Possible causes:
- Valid operating temperature range has been exceeded or is below
the valid temperature range
- Device defective
Remedies:
- Stay within valid temperature range
- Exchange the defective device.
Er.11: Value could not be calculated
Indicates a measuring value, needed for calculation of the display value, is faulty or out of range.
Possible causes:
- Incorrect scale
Remedies:
- Check settings and input signal