E30.0.0X.6C-11
Operating Manual GRA0420VO / GRA010VO
page 7 of 12
4.2 Selection of the output function
-
When pressing button 1 again, the display will show “
outP
“. (Output)
- Use button 2 and button 3 (middle or right button) to select the desired output-function.
Description
to select
as output
Output
(out)
see
chapter
no output, device is used as display
no
off
--
2-point-controller
2P
switching function
5.1
3-point-controller
AL
min-/max-alarm,
inverse
5.2
-
Press button 1 to validate the selected output function. The display shows “
outP
“ again.
For output function = no the configuration is now finished. Press button 1 to finish the adjustment and to
switch over to display the measuring value.
If the output function was changed here, the delay and preferred state of switching function and the switching
points / alarm-boundaries are to configured in following.
The settings described in the following depend on the output function. Depending on this setting therefore it
is possible that more than one point are present in the following.
- When pressing button 1 again, the
device will display “
1.dEL
“
(delay = delay of switching function)
.
- Use button 2 and button 3 to set the desired value for the switching-delay.
Hint: the selected value [0.01 ... 2.00] accords the switching delay in seconds.
- Press button 1 to validat
e the selection. The display shows “
1.dEL
“ again.
-
When pressing button 1 again, the device will display “
1.Err
“ (
error = preferred state of switching function
).
- Use button 2 and button 3 to set the desired initial state in case of an error.
Display
Preferred state of the output
Note
off
Inactive in case of an error
on
Active in case of an error
-
Press button 1 to validate the selection. The display shows “
1.Err
“ again.
The configuration of the output function is now completed. Depending on the selected output function you
have to make the settings for switching / alarm points. See description in chapter „switching points / alarm-
boundaries“ for further information.
Hint:
The settings for the switching and alarm points can be made later in an extra menu (see chapter 5)