Operating Manual GRA0420VO / GRA010VO 

page 12 of 12  

9  Specification 

 

GRA 0420 VO... 

GRA 010 VO... 

 

Input signal:

 

4 ... 20 mA (2-wire) 

0 ... 10V (3-wire) 

 

  

Voltage load:

 

< 5.5 V 

  Input resistance:

 

 

ca. 30 kOhm

 

max. permissible input:

 

25 mA (40mA short-time) 

20 V 

 

Supply voltage:

 

 

12 - 28 V 

 

Supply current:

 

from current loop 

< 10 mA 

 

    

Display:

 

approx. 7 mm high, 4-digit LED-display 

Display range:

 

first and last value freely adjustable 

  max. display value:

 

9999 digit 

  min. display value:

 

-1999 digit 

  recommended range:

 

< 2000 digit 

Decimal point:

 

any position 

Accuracy:

 (at 25°C)

 

< 0.2% ±1 digit 

Measuring rate:

 

approx. 50 measurements / second 

Filter:

 

selectable in 3 stages 

Operation:

 

via 3 buttons 

Min-/Max-value memory:

  via buttons selectable 

 

Switching outputs:

 

 

GRA 0420 VO: 

1 electrically isolated open collector output 
Test voltage:  50V 

GRA 010 VO: 

1 +Ub-switching open collector output 

Switching point, hysteresis

:

 

freely adjustable 

Switching voltage:

 

max. 28V 

Switching current:

 

max. 20mA  (optionally: 50mA) 

Please note: the switching output is not short-circuits protected

 

Reaction time:

 

< 20 ms 

Connection output:

 

via angle-type plug 

 

Nominal temperature:

 

25°C 

Working temperature:

 

-25 ... 50°C 

Relative humidity:

 

0 ... 80%  (non-condensing) 

Storage temperature:

 

-30 ... 85°C 

Electrical connection:

 

special-adapter design for cubic plug DIN 43650 for simple plug-in wherever 
required. 2 screws (68 and 75 mm) included in scope of supply 

Housing:

 

ABS, keypad 
approx. 48.5 x 48,5 x 35.5 mm (L x W x D) without angle-type plug 
approx. 50.5 x 90 x 39.5 mm (L x W x D) with angle-type plug 

Protection rating:

 

front IP65 (when mounted appropriately) 

EMC:

 

The device corresponds to the essential protection ratings established in the Regu-
lations of the Council for the Approximation of Legislation for the member countries 
regarding electromagnetic compatibility (2004/108/EG). 
In accordance with EA1 +A2 (appendix A, class B), 

additional fault: < 1% FS 

 

When connecting long leads adequate measures against voltage surges have 
to be taken.

 

10 Disposal instructions 

The device must not be disposed in the regular domestic waste. 
Send the device directly to us (sufficiently stamped), if it should be disposed. We will dispose the de-vice 
appropriate and environmentally sound. 

Summary of Contents for GRA 010 VO

Page 1: ...page 1 of 12 Manual for connection and operating of GRA 0420 VO GRA 010 VO as of version 1 2 GREISINGER electronic GmbH D 93128 Regenstauf Hans Sachs Stra e 26 Tel 0049 9402 9383 0 Fax 0049 9402 9383...

Page 2: ...TMENT 10 7 MIN MAX VALUE STORAGE 10 8 ERROR CODES 11 9 SPECIFICATION 12 10 DISPOSAL INSTRUCTIONS 12 1 Introduction The GRA0420VO and GRA010VO is a microprocessor controlled displaying monitoring and c...

Page 3: ...st be switched off and must be marked against using again in case of obvious malfunc tions of the device which are e g visible damage no prescripted working of the device storing the device under inap...

Page 4: ...ter is not as signed to contact 2 and if the Ub line is not assigned to contact 1 please do not forget to adjust the GRA angle type plug and the external angle type plug ac cordingly To do so open the...

Page 5: ...tation needed because of the high turn on current of high capacitive loads The same applies to incandescent lamps whose turn on current is also quite high due to their low cold resistance 3 2 1 GRA042...

Page 6: ...when a 20mA resp 10V input signal is attached Validate the selected value by pressing button 1 The display shows di Hi again Press button 1 again The display will show Li Limit Measuring range limit...

Page 7: ...ding on this setting therefore it is possible that more than one point are present in the following When pressing button 1 again the device will display 1 dEL delay delay of switching function Use but...

Page 8: ...troller AL min max alarm inverse 5 2 5 1 2 point controller This chapter describes how to configure the switching points as use the device for a 2 point controller This instruction demands that you se...

Page 9: ...on 2 and button 3 to set the desired delay of the alarm function Note the selected value 0 9999 accords the alarm delay in seconds The device will turn on the alarm after minimum or maximum alarm valu...

Page 10: ...slope adjustment The slope adjustment will be entered in The value displayed can be calculated like this Display measured value offset di Lo 1 slope adjustment 100 di Lo Example The setting is 2 00 th...

Page 11: ...signal Err 3 Display range has been exceeded Indicates that the valid display range 9999 digit of the device has been exceeded Possible causes Incorrect scale Remedies The error message will be reset...

Page 12: ...is not short circuits protected Reaction time 20 ms Connection output via angle type plug Nominal temperature 25 C Working temperature 25 50 C Relative humidity 0 80 non condensing Storage temperature...