5. MOUNTING AND INSTALLATION OF THE PELLET BURNER.
5.1.
MAIN REQUIREMENTS FOR INSTALLATION OF A PELLET BURNER FROM
SERIES ”GP XX SC”.
The following requirements must be observed during installation of a pellet burner from
series “GP xx sc”:
The burner must be positioned in a way providing enough free space for its cleaning
and maintenance;
The burner must be mounted to appliance (hot water boiler, or other heat energy
consumer) in a way providing availability for easy maintenance and cleaning of the
appliance;
It is not allowed to mount the burner to appliance, which has been installed in living
premises, including corridors;
The installation and mounting of the burner to appliance must be performed only by a
qualified technician;
The installation and maintenance of the automated pellet burner must be performed
by specialized companies which have acquired legal rights for such activities;
The automated pellet burner from series “GP xx sc” must be connected to the
electrical supply installation only by an authorized electrical technician;
Before initiation of the burner to operation, the heat energy consuming appliance’s
operational condition must be checked;
The burner attendance must be performed only by adult persons, which are well
familiar with the appliance’s manual for operation.
The mounting of the burner to a boiler (consumer-appliance) can be performed
through bolts (or studs) and nuts. The tightening of the burner has to be
performed by a tool (for example wrench). It is not allowed to fix it through
handles or others. The fixing and dismounting operations of the burner must be
performed by a qualified person equipped with proper tools.
5.2.
INSTALLATION OF THE PELLET BURNER.
The installation of the pellet burner from series “GP xx sc” to appliance requires preliminary
prepared technical project, complying with the acting provisions and regulations:
In case the consuming appliance is a hot water boiler, then the requirements
presented in standard BNS EN 303-5/2000 – “Hot water boilers for central heating
part 5 – Hot water solid fuel boilers with nominal heating output up to 300 kW –
terminology, tests and notifications”, must be observed;
In case the heat energy consuming appliance is not a hot water boiler, then the
requirements presented in the relevant standards for such type of appliances must be
observed;
Fire safety provisions;
About the electrical supply network – BNS EN 60335-1/1997 – “Securing of electrical
domestic appliances”.
When installing a pellet burner to a hot water boiler, please observe the relevant
chimney draught requirements, presented in the boiler’s technical data sheet.
5.3.
OVERALL DIMENSIONS OF THE BURNER’S MAIN MODULE.
Figure 5.1 and 5.2 present the overall dimensions of the burner’s main module, which have
to be taken in mind during the mounting and installation of the appliance.