Pellet burner GP 45 IV 23
6. INITIALIZATION OF AUTOMATED WOOD PELLET BURNER FROM SERIES “GP 45
IV” IN OPERATION.
The automated modulating pellet burner from series “GP 45 IV” must be initiated
in operation only by specialized company, authorized for such activities.
6.1.
MAIN REQUIREMENTS ABOUT THE USED FUEL.
To ensure complete fuel burning/utilization it is necessary to use only dry fuel. It is
recommended to store the fuel in dry ventilated premises;
It is forbidden to store the fuel next to the appliance to which the burner is mounted or
at distance less than 400 mm;
The optimal recommended distance between the appliance (to which the burner is
mounted) and the fuel is minimum 1000 mm. It is better to store the fuel in a neighbor
premise;
All fire safety requirements during the burner installation to the designated appliance
must be observed. It is recommended to have a fire-extinguisher on an easy
accessible and safe place.
6.2.
INITIALIZATION OF AUTOMATED WOOD PELLET BURNER FROM SERIES “GP
45 IV” IN OPERATION.
GENERAL CONDITIONS:
The burner handling must be performed in comply with the operation and
maintenance manual;
The operation mode of the system: pellet burner from series “GP” and heat energy
consumer must provide minimum under-pressure (pressure lower than the
atmospheric) in the appliance combustion chamber, within the range of 5-20 Pa;
Non compliance with this requirement might lead to emergency operation modes
or to inefficient burner operation. The under-pressure value in the combustion
chamber of the heat energy consuming appliance depends on the chimney
draught and other modules (for example flue gas extraction fan). Operation
modes not complying with this requirement could be indicated by the reversible
thermo-sticker temperature value.
Any intervention over the system operation, that might endanger the health of the
servicing personal or to any other indirectly related persons is forbidden;
During operation the burner must be periodically inspected by the servicing/handling
personal/customer;
The user must not perform repairs over the system’s modules. If a problem occurs
during its operation, the user must ask for competent assistance by a servicing
company;
It is forbidden to increase the burner heating output over its nominal output;
The ash residues from the burning process have to be gathered in fireproof
containers equipped with covers and after their cooling to ambient temperature
should be dumped at proper for the purpose places.