40
for North America
◆
The outdoor unit will not be embedded by the snow and not affected by garbage and oil smog;
◆
The installation of outdoor unit shall adopt rubber damping pad or spring damper to reduce noise and vibration;
◆
installation site;
◆
The installation shall be done by professional technicians.
3.5 Fixing and damping of unit
caused.
between the unit and foundation.
3.6 Outline dimension and position of installation hole
angel of ropes must be smaller than 40º during hanging and moving.
Unit:mm(inch)
Model
A
B
C
D
E
GMV-
HY
36WL
T
/
A
-T(U)
GMV-
HY
48WL
T
/
A
-T(U)
900(35-3/8) 340(13-3/8)
1345
(53)
572(22-1/2)
378
(15)
3.7 Installation space requirement
If all sides of the ODU (including the top) are surrounded by walls, process according to the following requirements for installation
space:
≥
350mm
(
13-3/4inch
)
(
78-3/4inch
)
(
8inch
)
(
8inch
)
(
78-3/4inch
)
(
13-3/4inch
)
(
8inch
)
≥
350mm
≥
200mm
≥
2000mm
Shockproof
material
≥
200mm
≥
200mm
≥
2000mm
Wall
Wall
Wall
Wall
4 Installation of indoor Unit
4.1 Installation of quiet design duct type indoor unit
Photovoltaic Direct-driven
VRF
Summary of Contents for R410A
Page 1: ...Photovoltaic Direct driven VRF for North America R410A GC201610 1 ...
Page 3: ...1 Photovoltaic Direct driven VRF for North America PRODUCT PRODUCT ...
Page 15: ...13 for North America CONTROL CONTROL Photovoltaic Direct driven VRF ...
Page 38: ...36 Photovoltaic Direct driven VRF for North America INSTALLATION ...
Page 61: ...MAINTENANCE for North America Photovoltaic Direct driven VRF 59 ...
Page 65: ...63 for North America Photovoltaic Direct driven VRF 3 Discharge temperature protection ...
Page 90: ...JF00303127 ...