9
for North America
PRODUCT
4.2.3 Features of Wall Mounted
Model
GMV-N07G/A3A-
D(U)
GMV-N09G/A3A-
D(U)
GMV-N12G/A3A-
D(U)
GMV-N18G/A3A-
D(U)
GMV-N24G/A3A-
D(U)
Product code
CM100N1480
CM100N1490
CM100N1500
CM100N1510
CM100N1520
Cooling Capacity
Btu/h
7500
9500
12000
18000
24000
kW
2.2
2.8
3.5
5.2
7
Heating Capacity
Btu/h
8500
11000
13500
20000
25500
kW
2.5
3.2
4
5.8
7.5
Galvanized Steel plate
Dimensions
(W×D×H)
outline
mm
843×180×275
843×180×275
940×200×298
940×200×298
1008×221×319
inch
33 1/5×7×10 5/6
33 1/5×7×10 5/6
37×7 7/8×11 3/4
37×7 7/8×11 3/4
39 2/3×8 5/7×12
5/9
Packaging
mm
973×258×370
973×258×370
1068×288×395
1068×288×395
1131×398×328
inch
38 1/3×10 1/6×14
4/7
38 1/3×10 1/6×14
4/7
42×11 1/3×15 5/9 42×11 1/3×15 5/9 44 1/2×15 2/3×13
Net Weight
lbs.
22
22
27.6
27.6
33.1
kg
10
10
12.5
12.5
15
Gross Weight
lbs.
27.6
27.6
33.1
33.1
40.8
kg
12.5
12.5
15
15
18.5
Pipe
Connections
Liquid Side
mm
Φ6.35
Φ6.35
Φ6.35
Φ6.35
Φ9.52
inch
Φ1/4
Φ1/4
Φ1/4
Φ1/4
Φ3/8
Gas Side
mm
Φ9.52
Φ9.52
Φ12.7
Φ12.7
Φ15.9
inch
Φ3/8
Φ3/8
Φ1/2
Φ1/2
Φ5/8
Drain Pipe
mm
Φ17
Φ17
Φ17
Φ17
Φ17
inch
Φ2/3
Φ2/3
Φ2/3
Φ2/3
Φ2/3
Power supply
1-phase 208-230V 60Hz
Fan
Type * Quantity
Driving Mechanism
Direct-driven
Motor Type
PG
Motor Power
Input
W
50
50
60
60
70
Motor Running
Current
A
0.2
0.2
0.21
0.21
0.31
Rate(H/M/L)
CFM
295/247/206
295/247/206
370/324/283
370/324/283
440/353/294
m
3
/h
500/420/350
500/420/350
630/550/480
630/550/480
750/600/500
Sound Pressure Level(H/M/L) dB(A)
38/34/30
38/34/30
44/41/38
44/41/38
44/41/38
Heat Exchanger
Air Filter
PP+10%BCM+FP03
Insulation Material
Foamed polystyrene
Refrigeration Control Device
EXV
Protection Device
Fuse
4.3 Operation range
Cooling
Outdoor temperature:
(
50
~1
29
°F
)
Heating
Outdoor temperature:
(
-22
~81°F
)
5 PRODUCT CAPACITY CORRECTION
5.1 Instruction of Product Capacity Correction
Nominal cooling capacity and nominal heating capacity are tested under given conditions:
(1) Rated cooling or heating condition
.
(2) No height difference between indoor unit and outdoor unit.
(3) Short connection pipe.
If the three conditions above have changed, the cooling and heating capacity will change correspondingly and correction is needed.
Photovoltaic Direct-driven
VRF
Summary of Contents for R410A
Page 1: ...Photovoltaic Direct driven VRF for North America R410A GC201610 1 ...
Page 3: ...1 Photovoltaic Direct driven VRF for North America PRODUCT PRODUCT ...
Page 15: ...13 for North America CONTROL CONTROL Photovoltaic Direct driven VRF ...
Page 38: ...36 Photovoltaic Direct driven VRF for North America INSTALLATION ...
Page 61: ...MAINTENANCE for North America Photovoltaic Direct driven VRF 59 ...
Page 65: ...63 for North America Photovoltaic Direct driven VRF 3 Discharge temperature protection ...
Page 90: ...JF00303127 ...