46
for North America
Photovoltaic Direct-driven
VRF
ODU
IDU
Pipe between
indoor branches
Total capacity of downstream indoor units C (Btu/h)
Gas pipe(mm/inch)
Liquid pipe(mm/inch)
C
≤
19000
Φ12.7(1/2)
Φ6.35(1/4)
19000
<
C
≤
48500
Φ15.9(5/8)
Φ9.52(3/8)
48500
<
C
≤
75000
Φ19.05(3/4)
Φ9.52(3/8)
6.5 Dimension of Pipe between Indoor Branch and IDU
Dimension of pipe between indoor branch and IDU should be consistent with the dimension of indoor pipe.
ODU
IDU
Indoor branches
Pipe between indoor branch and IDU
Rated capacity of IDU C
(Btu/h)
Gas pipe(mm/inch)
Liquid pipe(mm/inch)
C
≤
9600
Φ9.52(3/8)
Φ6.35(1/4)
9600
<
C
≤
17000
Φ12.7(1/2)
Φ6.35(1/4)
17000
<
C
≤
48000
Φ15.9(5/8)
Φ9.52(3/8)
48000
<
C
≤
55000
Φ19.05(3/4)
Φ9.52(3/8)
55000
<
C
≤
96000
Φ22.2(7/8)
Φ9.52(3/8)
NOTICE!
If the distance between IDU and its nearest branch is over 10m(33feet), then the
liquid pipe of IDU (rated capacity ≤17000Btu/h) shall be enlarged.