GREE AIR SOURCE HEAT PUMP WATER HEATER SERVICE MANUAL
22
configurable parameter codes and values. Press
▲ or ▼
to select P5 and press the
MODE
button. Then
item value 00 or 01 blinks under the parameter code P5. Press
▲ or ▼
to select the item value and press
the
MODE
button to confirm setting (00:
℃
and 01:
℉
). After that, press the
FUNCTION
button to return
to the main interface. If no operation is performed with 15s, it will switch back to the main interface
automatically.
Note: Other parameters cannot be modified; otherwise, operation exception will be caused.
4.8 Errors Display
When some errors occur during operation, the error codes will be displayed on the controller.
Meanwhile, the unit is in the Off state and the controller supports only the on/off and query functions.
If multiple errors occur to the water heater simultaneously, the corresponding error codes will be
displayed circularly.
If the controller displays a error, shut down the water heater and contact qualified personnel for
maintenance. The following figure shows a communication error.
For details on error codes, see the table attached at the end of this manual.
NOTES: Controller ZF5201 refer to the operational method ibidem.
Summary of Contents for GRS-1.5/D150ANbA-K
Page 3: ...GREE AIR SOURCE HEAT PUMP WATER HEATER SERVICE MANUAL 1 PRODUCT ...
Page 11: ...GREE AIR SOURCE HEAT PUMP WATER HEATER SERVICE MANUAL 9 CONTROL ...
Page 25: ...GREE AIR SOURCE HEAT PUMP WATER HEATER SERVICE MANUAL 23 INSTALLATION ...
Page 47: ...GREE AIR SOURCE HEAT PUMP WATER HEATER SERVICE MANUAL 45 COMMISSIONING and TRIAL RUN ...
Page 55: ...GREE AIR SOURCE HEAT PUMP WATER HEATER SERVICE MANUAL 53 MAINTENANCE ...
Page 70: ...GREE AIR SOURCE HEAT PUMP WATER HEATER SERVICE MANUAL 68 UNIT MAINTENANCE ...
Page 81: ...JF00303641 ...