GREE AIR SOURCE HEAT PUMP WATER HEATER SERVICE MANUAL
57
E6 Communication fault
Check whether the
Communication cable is
correctly connected.
Check whether the wired
controller is normal.
Check whether the
Communication cable is
accessible.
Re-connect the
communication cable.
Replace the
Communication cable.
Replace the wired
controller.
N
Y
N
Y
Y
Replace the wired
controller.
N
2.4 F3, F4, F6, Fd, FE, FL Temperature sensor Fault
Fault error: F3, F4, F6, Fd, FE, or FL (one or more of these codes may be displayed), for example,
Applicable mode: all modes
Fault judgment condition and method: F3, F4, F6, Fd, FE, or FL is displayed on the wired controller
(F3: Outdoor ambient temperature
sensor fault; F4: Air exhaust temperature
sensor fault; F6: Pipe
temperature
sensor fault (for outdoor heat exchanger); Fd: Air intake temperature
sensor fault; FE: Upper
temperature
sensor fault of the water tank; FL: Lower temperature
sensor fault of the water tank). The
troubleshooting method is shown in the flowchart below.
Possible cause:
(1) Incorrect connection of temperature
sensor; (2) Temperature
sensor fault; (3) Mainboard fault
Troubleshooting:
Summary of Contents for GRS-1.5/D150ANbA-K
Page 3: ...GREE AIR SOURCE HEAT PUMP WATER HEATER SERVICE MANUAL 1 PRODUCT ...
Page 11: ...GREE AIR SOURCE HEAT PUMP WATER HEATER SERVICE MANUAL 9 CONTROL ...
Page 25: ...GREE AIR SOURCE HEAT PUMP WATER HEATER SERVICE MANUAL 23 INSTALLATION ...
Page 47: ...GREE AIR SOURCE HEAT PUMP WATER HEATER SERVICE MANUAL 45 COMMISSIONING and TRIAL RUN ...
Page 55: ...GREE AIR SOURCE HEAT PUMP WATER HEATER SERVICE MANUAL 53 MAINTENANCE ...
Page 70: ...GREE AIR SOURCE HEAT PUMP WATER HEATER SERVICE MANUAL 68 UNIT MAINTENANCE ...
Page 81: ...JF00303641 ...