Photovoltaic Direct-driven Inverter VRF
54
(3) Setting of residual power sending to the grid
After entering this function setting, default display of master unit is as below. Other basic
modules will display according to normal operation mode:
LED1
LED2
LED3
Function
Code
Display
Mode
Current
Progress
Display
Mode
Current
Status
Display
Mode
qn
On
00
Flicker
oC
Flicker
Press SW1 ▲ button and SW2 ▼ button to select the following setting of residual power
sending to the grid
LED1
LED2
LED3
Function
Code
Display
Mode
Setting of
residual power
sending to the
grid
Display
Mode
Current
Status
Display Mode
qn
On
1~2
Flicker
oC
Flicker
After selecting corresponding setting of residual power sending to the grid, press SW7 to
confirm the selected mode. Corresponding display of all modules are as below:
LED1
LED2
LED3
Function
Code
Display
Mode
Setting of
residual power
sending to the
grid
Display
Mode
Current
Status
Display Mode
qn
On
1~2
On
oC
On
Master unit will memorize this setting and the setting won’t be cleared in power failure.
For the master unit in this case, press SW6 return button to return to the operation of last
step.
For the master unit in this case, if no button is pressed for 5min continuously, it will exit
automatically and the unit will resume the display of current status.
Note:
No.
Grid connection function
1
Residual power sending to the grid (defaulted)
2
Residual power no sending to the grid
Description of each stage of debugging progress
——
Debugging code Progress code
Status code
Meaning
progress
LED1
LED2
LED3
Code
Display
status
code
Display
status
Code
Display
status
01_Set up
master unit
db
light
01
light
A0
light
System is not debugged.
db
light
01
light
CC
light
System doesn’t have master unit. Reset
master unit.
db
light
01
light
CF
light
More than 2 master units are set. Reset
master unit.
db
light
01
light
OC
light
Master unit is successfully set. Start
next progress.