Photovoltaic Direct-driven Inverter VRF
25
Fig.4.3.1
1) Align the expansion end of copper pipe with the center of threaded joint. Tighten the
flare nuts with your hands.
2) Tighten the flare nuts with torque wrench until you hear "click" sound.
3) Use sponge to wrap the connecting pipe and joints without thermal insu lation and tie it
up with plastic tape.
4) A mounting support for the connection pipe is required.
5) The curvature degree of connection pipe should not be small, otherwise the pipe might
crack. Installation personnel should use tube bender when bending th e pipe.
6) Don't forbibly stretch the pipe joint, otherwise indoor capillary or other pipes might be
damaged and lead to refrigerant leakage.
4.3.2 Manifold
(1) Y-type manifold, See the Fig. 4.3.2(a). T-type manifold, See the Fig. 4.3.2(b).
Fig. 4.3.2(a)
Fig. 4.3.2(b)