Photovoltaic Direct-driven Inverter VRF
57
Description of each stage of debugging progress
——
Debugging
code
Progress code
Status code
Meaning
progress
LED1
LED2
LED3
Code
Display
status
code
Display
status
Code
Display
status
16_Heating
debugging
db
light
16
light
AH
light
Debugging is enabled in heating
mode (debugging mode,
auto-selected by system).
db
light
16
light
Error
code
light
Error occurs during debugging in
heating mode.
db
light
16
light
J0
light
Error of other modules occurs during
debugging in heating mode.
db
light
16
light
U9
light
Outdoor pipeline and valves are not
normal.
db
light
16
light
XXXX/
U8
light
System detects error in indoor
pipeline. XXXX is the project no. of
the faulted IDU. 3s later, error code
U8 is displayed. For e xample, IDU no.
100 has U8 error, then LED3 displays
like this: 01 (2s later) 00 (2s later) U8 ,
and repeat again.
17_Debugging
finished
01~0
4
light
OF
light
OF
light
Debugging is finished. System is on
standby condition. LED1 displays
module address. LED2 and LED3
display “OF”.
5.2.2.3 Debugging operation mode
Gree Photovoltaic Direct-driven Inverter VRF System
has two debugging modes: one is
direct operation on main board of outdoor units while the other is PC operation via special
software. In PC software debugging, indoor/outdoor parameters can be displayed and historical
data can be recorded and inquired. (Operation details can be found in relevant instruction
manuals)
(1)Debugging through operation on main board of outdoor units
In this debugging mode, following debugging functions are included on the main board:
Step 1:
front panel of the outdoor units must be fully closed. Open the debugging window
of each basic module;
Step 2:
disconnect power for outdoor units. According to design requirements of external
static pressure, set up corresponding static pressure mode for the units. Setting methods can
be seen in Outdoor Fan Static Pressure Setup SA6_ESP_S;
Step 3:
disconnect power for outdoor units and set one module as a master unit. Setting
methods can be seen in Master Unit Setup SA8_MASTER_S;
Step 4:
Connect power for all indoor units. Make sure all IDUs are power on. Then all
outdoor modules will display “Debugging not enabled”;
Step 5:
Find the module with “01” module address to be the master module. Hold SW7
Summary of Contents for GMV-Y120WM/C-F