Photovoltaic Direct-driven Inverter VRF
18
(4) If the length between an IDU and its nearest branch is above 10m(32 -4/5ft.), then
increase the size of the liquid pipe of IDU (only for the pipe size that is≤6.35mm(1/4in.).
4.2.4 Connection Pipe among Outdoor Modules
Fig.4.2.5
Unit: m(ft.)
Fig.4.2.6
NOTICE!
When the distance between outdoor units exceeds 2m (6-1/2ft.), U-type oil trap
should be added at low-pressure gas pipe. A+B
≤
10m (32-7/8ft.).