61
DC Inverter Multi
VRF Service Manual
Installation of outdoor unit
Select the installing position correctly.
Build the foundation according to the anchor bolt
position and the dimension of outdoor unit;
Build the damping device properly.
Avoid sharp knock when handling the outdoor unit. The
inclination angle shall not be higher than 15°
Connection of indoor unit and outdoor unit
Tighten the nuts;
Provide proper protection to the outdoor connection
pipe, communication wires and power supply.
Leakage detection under pressure
.HHSWKHSUHVVXUHIRUKRXUV([FHSWIRUWKHLQÀXHQFHE\WHPSHUDWXUH
it is deemed acceptable if pressure drop is within 0.02MPa. (With the
temperature change by 1 , the pressure will change by approx. 0.01MPa).
Vacuuming
Establish vacuum simultaneously in the gas pipe and liquid pipe;
The vacuuming time shall be long enough.
Put still for 1 hour after vacuuming. It is deemed
acceptable if the pressure will not rise.
Add refrigerant
$GGUHIULJHUDQWDFFRUGLQJWRWKHYROXPHDVVSHFL¿HGRQWKHHQJLQHHULQJGUDZLQJ
Open the valve of outdoor unit
Commissioning of complete unit
Remarks:
1) Described above are general working procedures. The procedures might vary with the site conditions.
2) For detailed installation rules, please see the description in each chapter.
Summary of Contents for GMV-PD100W/NAB-K
Page 1: ...DCINVERTERMULTIVRF SERVICE MANUAL T1 R410A 50Hz GC201112 CENTRAL AIR CONDITIONERS...
Page 5: ...1 DC Inverter Multi VRF Service Manual PRODUCT QSPEVDU...
Page 11: ...7 DC Inverter Multi VRF Service Manual CONTROL DPOUSPM...
Page 62: ...58 DC Inverter Multi VRF Service Manual INSTALLATION...
Page 99: ...95 DC Inverter Multi VRF Service Manual MAINTENANCE...
Page 118: ...114 DC Inverter Multi VRF Service Manual GMV Pd140W NaB M GMV Pd160W NaB M...
Page 133: ...JF00300208...