107
DC Inverter Multi
VRF Service Manual
2.10 IPM Protecion
Yes
Yes
Yes
Yes
No
No
No
No
No
Yes
E5 is displayed on
the wired controller
IPM protection
Monitoring
display
Nixie tube of
mainboard
It is recorded
Is it wet,dirty or
short-circuit?
Inspect the mainboard 1 min
after power off or the buss
voltage is below 36V
Dry, and clean it or
remove short circuit.
Restart the unit.
Does it work normally?
1. If it is affected by damp, find out the
reason and take some precautionary
measures. After drying the mainboard
,
brush it with damp proof gum water
.
2. If it is polluted, find out the reason
and protect it from dust . If the
environment is bad , clean the dirt
periodically.
3. If it is short-circuit, find out the
Is IPM
module of mainboard
damaged?
Display H5
Replace mainboard
Is compressor
wire loose or is phase
sequence wrong?
Tighten the
compressor wire or adjust
the phase sequence
reason and clean the electric box so
as to prevent the conductive matter
such as iron chippings adhering on
the board
Is + 15V
of mainboard stable?
15VA-pin 1,2
Summary of Contents for GMV-PD100W/NAB-K
Page 1: ...DCINVERTERMULTIVRF SERVICE MANUAL T1 R410A 50Hz GC201112 CENTRAL AIR CONDITIONERS...
Page 5: ...1 DC Inverter Multi VRF Service Manual PRODUCT QSPEVDU...
Page 11: ...7 DC Inverter Multi VRF Service Manual CONTROL DPOUSPM...
Page 62: ...58 DC Inverter Multi VRF Service Manual INSTALLATION...
Page 99: ...95 DC Inverter Multi VRF Service Manual MAINTENANCE...
Page 118: ...114 DC Inverter Multi VRF Service Manual GMV Pd140W NaB M GMV Pd160W NaB M...
Page 133: ...JF00300208...