67
DC Inverter Multi
VRF Service Manual
5.2 Three Principles of Refrigerant Piping Installation
Observe the three principles of refrigerant piping:
Key Factors
Measures to Avoid Failure
Dry
Invasion of outside water
Example: Rainwater, engineering water
Invasion of indoor condensate
Fabrication of
¿WWLQJSLSH
Vacuuming and
drying
Purge
Clean
Formation of oxides inside
the pipe during welding
Invasion of dust and foreign
articles from outside
Fabrication of
¿WWLQJSLSH
Purge
Expel with nitrogen 0.05~0.3Mpa
Airtight
Incomplete welding
/HDNDJHIURPÀDUHGSRUW
Leakage from edge
Use suitable materials (copper tube,
soldering bar)
Observe the basic operations
IRUÀDULQJRI¿WWLQJSLSH
Observe the basic welding procedures
Observe the basic inerfacting procedures
Airtight test
5.3 Installation of Metal Embedded Pipe
Work Order
Metal Embedding Diagram
Installation of metal Embedded Parts
Plotting
Plot the line on ground if possible and use laser to project it onto the roof. This is quick and correct.
Advance Installation of Metal Embedded Parts
Please select according to local codes.
Subsequent Installation of Expansion Bolts
In case that the metal embedded parts cannot be used due to design change, the expansion bolts may
be used.
Subsequent Installation of Expansion Bolts
The foot pedal shall be supported on three points if exceeding 2m.
7KHIRRWSHGDOPXVWEH¿[HGVHFXUHO\WRWKHODGGHU
Please do not work on the top of ladder.
5.4 Installation of Carriage of Refrigerant pipin
5.4.1 Fixing of horizontal pipe
The refrigerant pipe will extend and shrink with each start or stop of the air conditioner unit (5~10 times /
hour). Under a temperature difference of 80 , this extension may reach 13.84mm for every 10m. To prevent
failure, the pipes must be reinforced as follows.
Spacing between supports
Outer diameter of pipe (mm)
6.35-8.52
Over 12.7
Spacing between supports (m)
Below 1.2
Below 1.5
Note:
If the gas pipe and liquid pipe are suspended together, the size of liquid pipe shall prevail
CAUTION
1HYHUPDNHWKHSLSHGLUHFWO\FRQWDFWZLWKWKH¿[LQJPHWDOSDUWV7KHUPDOLQVXODWLRQVKDOOEHSURYLGHG
DURXQGWKH¿[LQJPHWDOSDUWVRWKHUZLVHFRQGHQVLQJZLOORFFXU
Summary of Contents for GMV-PD100W/NAB-K
Page 1: ...DCINVERTERMULTIVRF SERVICE MANUAL T1 R410A 50Hz GC201112 CENTRAL AIR CONDITIONERS...
Page 5: ...1 DC Inverter Multi VRF Service Manual PRODUCT QSPEVDU...
Page 11: ...7 DC Inverter Multi VRF Service Manual CONTROL DPOUSPM...
Page 62: ...58 DC Inverter Multi VRF Service Manual INSTALLATION...
Page 99: ...95 DC Inverter Multi VRF Service Manual MAINTENANCE...
Page 118: ...114 DC Inverter Multi VRF Service Manual GMV Pd140W NaB M GMV Pd160W NaB M...
Page 133: ...JF00300208...