26
DC Inverter Multi
VRF Service Manual
DPOUSPM
17
Lock
Region monitoring controller
A: Inquiry state: “LOCK” is displayed when selected indoor unit is locked.
B: Control state: “LOCK” is displayed during setting or giving the lock order.
Region wired controller: “LOCK” is displayed when selected
unit is locked in long-distance monitoring.
18
(set temp.)
Set temp. value is displayed when the selected indoor unit
is on and not in timer inquiry or setting status.
19
HR (hour)
“HR” is displayed during timer inquiry or setting.
20
.5
“.5” is displayed when the timer time value includes 0.5 hr
and the unit is during timer inquiry or setting.
Note:
1) Contents in the double quotation marks indicate the display in LCD. Following part is the same to it.
2) Online indoor units to Mini Centralized Controller indicate that in a region. Following part is the same to it.
3) No signal control function for region wired controller, and “SINGLE” won’t be displayed either.
5.4 Connection Between Controller and Unit
Insert the 4-core twisted pair line to wired controller, if which is with the indoor unit, into region controller
wiring terminal CN1 (or CN2), and then connect the other wiring terminal CN2 (or CN1) with the main board of
indoor unit.
If there is no wired controller with indoor unit, introduce a 4-core twisted pair line to indoor unit main board
and connect it with region controller wiring terminal CN1 (or CN2).
Note:
Any main board of the indoor unit controlled by the region controller can be connected. If the region
controller is used as a region wired controller, wired controller with the indoor unit must be removed.
Region Controller
CN1
CN2
Optional connection
4-core twisted pair line
4-core twisted pair line
1
1
1
1
Main board of Indoor unit
4-core communication line terminal.
Wired controller or region controller
4-core communication line terminal.
Fig.5.4 Power cords and communication lines for region controller
Before installation and connection, make sure the power supply is off. After installation and connection,
check the connection result again to prevent loose or short.
There are 4 connection lines (included in the 4-core twisted pair line) to the controller, from CN1 or
the upper and right CN2 to the upper they respectively are: Ground line (GND), communication line A (A),
communication line B(B) and power cord (+12 v).
Summary of Contents for GMV-PD100W/NAB-K
Page 1: ...DCINVERTERMULTIVRF SERVICE MANUAL T1 R410A 50Hz GC201112 CENTRAL AIR CONDITIONERS...
Page 5: ...1 DC Inverter Multi VRF Service Manual PRODUCT QSPEVDU...
Page 11: ...7 DC Inverter Multi VRF Service Manual CONTROL DPOUSPM...
Page 62: ...58 DC Inverter Multi VRF Service Manual INSTALLATION...
Page 99: ...95 DC Inverter Multi VRF Service Manual MAINTENANCE...
Page 118: ...114 DC Inverter Multi VRF Service Manual GMV Pd140W NaB M GMV Pd160W NaB M...
Page 133: ...JF00300208...