97
DC Inverter Multi
VRF Service Manual
F4
Outdoor ambient
temperature
sensor error
Outdoor
environment
sensor
Test for 30 seconds successively to check if the temperature sensor is disconnected.
If yes, alarm will be sent; otherwise no processing will be made. If the controller
of outdoor unit detects failure of outdoor sensor under open circuit, short circuit
and excess of test value, the outdoor unit will execute the following default
actions, that is, the error message will be sent to each indoor unit and the error
code will be displayed via error indicator or wired controller. When the outdoor
ambient temperature is lower than -5 , the disconnection failure of outdoor
inlet, middle and exit sensors in shield room will be processed as under -30 .
F7
Outdoor defrost
temperature
sensor error
Outdoor Defrost
Sensor
Test for 30 seconds successively to check if the temperature sensor is disconnected.
If yes, alarm will be sent; otherwise no processing will be made. If the controller
of outdoor unit detects failure of outdoor sensor under open circuit, short circuit
and excess of test value, the outdoor unit will execute the following default
actions, that is, the error message will be sent to each indoor unit and the error
code will be displayed via error indicator or wired controller. When the outdoor
ambient temperature is lower than -5 , the disconnection failure of outdoor
inlet, middle and exit sensors in shield room will be processed as under -30 .
F9
Exhaust
temperature
sensor error
Exhaust
temperature
sensor
Test for 30 seconds successively to check if the temperature sensor is disconnected.
If yes, alarm will be sent; otherwise no processing will be made. If the controller
of outdoor unit detects failure of outdoor sensor under open circuit, short circuit
and excess of test value, the outdoor unit will execute the following default
actions, that is, the error message will be sent to each indoor unit and the error
code will be displayed via error indicator or wired controller. When the outdoor
ambient temperature is lower than -5 , the disconnection failure of outdoor
inlet, middle and exit sensors in shield room will be processed as under -30 .
1.2 Display Code on Digital Tube of Outdoor Mainboard
Error
Display
on Digital
Tube
Display on
Indoor Unit
Error
Display
on
Digital
Tube
Display on
Indoor Unit
DC overvoltage protection
PH
E5
Input overcurrent protection
PA
E5
Module overheat protection
P8
E5
Jumper fault
C5
No display
Current test circuit fault
Pc
E5
Recharging circuit fault
PU
E5
Module temperature sensor fault
P7
E5
High-pressure protection
E1
E1
Compressor overcurrent protection
P5
E5
Low-pressure protection
E3
E3
DC undervoltage protection
PL
E5
Exhaust protection
E4
E4
Compressor startup failure
Lc
E5
Compressor overload protection
H3
E5
PFC module protection
Hc
E5
Communication fault (between indoor
/ outdoor unit and wired controller)
E6
E6
Drive resetting and stop
P0
E5
Outdoor ambient temperature
sensor error
F4
F4
Protection of compressor against
loss of synchronization
H7
E5
Indoor coil inlet temperature
sensor error
F5
F5
Compressor protection
against loss of phase
Ld
E5
Indoor coil middle temperature
sensor error
F6
F6
Inverter drive communication fault
P6
E5
Outdoor coil outlet
temperature sensor error
F7
F7
IPM module protection
H5
E5
Exhaust temperature sensor error
F9
F9
Summary of Contents for GMV-PD100W/NAB-K
Page 1: ...DCINVERTERMULTIVRF SERVICE MANUAL T1 R410A 50Hz GC201112 CENTRAL AIR CONDITIONERS...
Page 5: ...1 DC Inverter Multi VRF Service Manual PRODUCT QSPEVDU...
Page 11: ...7 DC Inverter Multi VRF Service Manual CONTROL DPOUSPM...
Page 62: ...58 DC Inverter Multi VRF Service Manual INSTALLATION...
Page 99: ...95 DC Inverter Multi VRF Service Manual MAINTENANCE...
Page 118: ...114 DC Inverter Multi VRF Service Manual GMV Pd140W NaB M GMV Pd160W NaB M...
Page 133: ...JF00300208...