![Gree GMV-PD100W/NAB-K Service Manual Download Page 17](http://html1.mh-extra.com/html/gree/gmv-pd100w-nab-k/gmv-pd100w-nab-k_service-manual_2260354017.webp)
13
DC Inverter Multi
VRF Service Manual
DPOUSPM
Absolute pressure
value for discharge( )
P 30
30
P 42
42
P 49
P 49
Cooling
Shutdown the
fan forcibly
Turn down one grade (not
including stopping windshield )
Remain
Turn up
one grade
For ultra-high fan speed, you couldn’t turn up the grade anymore;
Heating Mode:
The fan should run at high fan speed for 35s before the compressor is started, meanwhile, it is not
allowed to turn up to ultra-high fan speed within the earlier 3 minutes after the compressor started, but it could
be switched to low speed and stopping fan. You could turn up to the highest level ultra-high fan speed after 3
minutes.
Pressure section:
Absolute pressure value
for discharge( )
P 37
37
P 48
3
Heating
Turn up one grade
Remain
Turn down one grade
4) Defrosting Function
Defrosting Start Conditions
Keep heating (the four-way valve is under the heating position) for 50 minutes; when the intermediate
VHQVRUWHPSHUDWXUHDQGRXWGRRUDPELHQWWHPSHUDWXUHUHWDLQWKHIROORZLQJFXUYH¿JXUHIRUV
Temperature
of
Mid.
Temp.
sensor
Outdoor Dry-bulb Temperature
-10
-15
-10
-5
0
-5
0
5
10
Or the outdoor ambient temperature is below -6 ; and keeps heating (the four-way valve is under the
heating position) for 2 hours;
Defrosting Stop Conditions:
Outdoor coil pipe temperature is higher than 15 or the defrosting is running for 10 minutes continuously.
Defrosting Movements:
The defrosting is made by switching four-way valve to cooling mode.
Summary of Contents for GMV-PD100W/NAB-K
Page 1: ...DCINVERTERMULTIVRF SERVICE MANUAL T1 R410A 50Hz GC201112 CENTRAL AIR CONDITIONERS...
Page 5: ...1 DC Inverter Multi VRF Service Manual PRODUCT QSPEVDU...
Page 11: ...7 DC Inverter Multi VRF Service Manual CONTROL DPOUSPM...
Page 62: ...58 DC Inverter Multi VRF Service Manual INSTALLATION...
Page 99: ...95 DC Inverter Multi VRF Service Manual MAINTENANCE...
Page 118: ...114 DC Inverter Multi VRF Service Manual GMV Pd140W NaB M GMV Pd160W NaB M...
Page 133: ...JF00300208...