GREE DC Inverter Side Discharge VRF
Ⅱ
for North America
129
Removal operation of compressor
Remark: Before removing the compressor, please make sure that there’s no refrigerant inside the pipeline and the
power is disconnected.
Process
Photo
Operation Instruction
4. Remove the
compressor from
chassis
Take out the
compressor and
replace it
Note: When replacing
the compressor, do
not damage nearby
pipelines and other
parts
5. Fix the new
compressor at the
chassis
After replacing the
compresor, fix the
nuts at the bottom of
compressor
6. Connect suction
pipe and
discharge pipe of
copressor and
pipeline of system
again
Weld the connection
pipe of compressor,
connect the pipeline
and compressor
Note: During welding
process, do not let
flame burn out other
parts
Summary of Contents for GMV-24WL/C-T
Page 4: ...GREE DC Inverter Side Discharge VRF for North America 1 PRODUCT...
Page 12: ...GREE DC Inverter Side Discharge VRF for North America 9 CONTROL...
Page 17: ...GREE DC Inverter Side Discharge VRF for North America 14...
Page 18: ...GREE DC Inverter Side Discharge VRF for North America 15 Button Graphics...
Page 65: ...GREE DC Inverter Side Discharge VRF for North America 62 Switchover of Software Languages...
Page 66: ...GREE DC Inverter Side Discharge VRF for North America 63 INSTALLATION...
Page 98: ...GREE DC Inverter Side Discharge VRF for North America 95 MAINTENANCE...
Page 150: ...JF00302320...