GREE DC Inverter Side Discharge VRF
Ⅱ
for North America
119
Removal operation of compressor
Remark: Before removing the compressor, please make sure that there’s no refrigerant inside the pipeline and the
power is disconnected.
Process
Photo
Operation Instruction
3. Loose nuts
fixing the foot of
compressor
Twist off the nuts for
compressor with
wrench
4. Remove the
compressor
from the chassis
● Take out the
compressor and
replace it
Note: When replacing
the compressor, do
not damage nearby
pipelines and other
parts
5. Fix the new
compressor at the
chassis
After replacing the
compresor, fix the
nuts at the bottom of
compressor
6. Connect suction
pipe and
discharge pipe of
copressor and
pipeline of system
again
Weld the connection
pipe of compressor,
connect the pipeline
and compressor
Note: During welding
process, do not let
flame burn out other
parts