GREE DC Inverter Side Discharge VRF
Ⅱ
for North America
68
3.3 Carrying and installing outdoor unit
When carrying the outdoor unit, hang the unit in four directions with two sufficient ropes. In order to
avoid excursion from the center, the angel of ropes must be smaller than 40º during hanging and
moving.
3.4 Installation notices
In order to ensure proper operation, the selection of installation site must conform to the following
principle:
(1) The discharged air of outdoor unit will not flow back and there is sufficient space around the unit
for maintenance;
(2) The installation site must be well ventilated to ensure sufficient air intake and discharge. Make
sure there is no obstacle at the air inlet and air outlet. If there is any obstacle, please remove it;
(3) The installation site shall be able to withstand the weight of outdoor unit and capable for
soundproof and vibration. The air outlet and noise of unit will not affect neighbors;
(4) The hanging of outdoor unit must use appointed hanging hole. Pay attention to protect the unit
during hanging and installation. Prohibit hitting the sheet metal to avoid rust in the future.
(5) Avoid direct sunlight;
(6) The rain and condensation water can be drained out smoothly;
(7) The outdoor unit will not be embedded by the snow and not affected by garbage and oil smog;
(8) The installation of outdoor unit shall adopt rubber damping pad or spring damper to reduce
noise and vibration;
(9) The installation dimension shall accord with the installation requirement of this manual and the
outdoor unit must be fixed at the installation site;
(10) The installation shall be done by professional technicians.
3.5 Fixing and damping of unit
The outdoor unit shall be fixed with 4 M12 bolts and closely contacted with the foundation.
Otherwise, big vibration and noise will be caused.
The outdoor unit shall be fixed firmly. The rubber board with thickness over 20mm or corrugated
rubber damping pad shall be applied between the unit and foundation.
3.6 Outline dimension and position of installation hole
When carrying the outdoor unit, hang the unit in four directions with two sufficient ropes. In order to
avoid excursion from the center, the angel of ropes must be smaller than 40º during hanging and
moving.
Summary of Contents for GMV-24WL/C-T
Page 4: ...GREE DC Inverter Side Discharge VRF for North America 1 PRODUCT...
Page 12: ...GREE DC Inverter Side Discharge VRF for North America 9 CONTROL...
Page 17: ...GREE DC Inverter Side Discharge VRF for North America 14...
Page 18: ...GREE DC Inverter Side Discharge VRF for North America 15 Button Graphics...
Page 65: ...GREE DC Inverter Side Discharge VRF for North America 62 Switchover of Software Languages...
Page 66: ...GREE DC Inverter Side Discharge VRF for North America 63 INSTALLATION...
Page 98: ...GREE DC Inverter Side Discharge VRF for North America 95 MAINTENANCE...
Page 150: ...JF00302320...