4.3.2.3 Operation instruction
(1) Power LED: a red light. If the red light is on, it indicates normal power supply. If the red light is
off, it indicates the power supply of converter is not normal.
(2) Communication LEDs: yellow lights. When converter is working and the computer is
transmitting data, the TX data transmitting light will be flickering. When units are uploading data
to the computer, the RX data receiving light will be flickering.
(3) When converter is under RS485 data transferring mode, the function LED of RS485 to USB will
be on.
(4) When converter is under CAN data transferring mode, the function LED of CAN to USB will be
on.
(5) When converter is under HBS data transferring mode, the function LED of HBS to USB will be
on.
(6) USB interface: connect USB data wire.
(7)
CAN interface: When converter is under CAN communication mode, connect air conditioner’s
CAN data interface. CAN interface exhibits no polarity (A and B are equal).
(8) HBS interface: When HBS converter is under HBS communication mode, connect air
conditioner’s HBS data interface. HBS interface exhibits no polarity (This interface is not yet
available for Gree debugger and the monitoring software).
(9) RS485 interface: When RS485 converter is under RS485 communication mode, connect air
conditioner’s RS485 data interface. RS485 interface exhibits polarity and terminal A and B are
different.
Summary of Contents for GMV-24WL/C-T
Page 4: ...GREE DC Inverter Side Discharge VRF for North America 1 PRODUCT...
Page 12: ...GREE DC Inverter Side Discharge VRF for North America 9 CONTROL...
Page 17: ...GREE DC Inverter Side Discharge VRF for North America 14...
Page 18: ...GREE DC Inverter Side Discharge VRF for North America 15 Button Graphics...
Page 65: ...GREE DC Inverter Side Discharge VRF for North America 62 Switchover of Software Languages...
Page 66: ...GREE DC Inverter Side Discharge VRF for North America 63 INSTALLATION...
Page 98: ...GREE DC Inverter Side Discharge VRF for North America 95 MAINTENANCE...
Page 150: ...JF00302320...