GREE DC Inverter Side Discharge VRF
Ⅱ
for North America
85
(2) The wiring diagram for power cord of outdoor unit and communication wire.
There are two wiring diagrams for communication wires of indoor/outdoor units and remote monitor:
1) Real line method;
2) Broken line method. Please select it based on the actual installation situation.
There are two wiring diagrams for power cord:
1) Real line method;
2) Broken line method. Please select it based on the actual installation situation.
7.2 Power Cable Wire Gauge and Circuit Breaker Selection
Model
Power supply
Max Fuse Size/Fusible
Max.
(A)
Max Ckt, Bkr Size/Disjoncteur
Max. (A)
Min. Circuit
Ampacity
(A)
GMV-24WL/C-T(U)
208/230V~
60Hz
25
25
21
GMV-28WL/C-T(U)
208/230V~
60Hz
30
30
21
GMV-36WL/A-T(U)
208/230V~
60Hz
35
35
31
GMV-48WL/A-T(U)
208/230V~
60Hz
45
45
34
GMV-60WL/A-T(U)
208/230V~
60Hz
60
60
39.8
GMV-36WL/C-T(U)
208/230V~
60Hz
35
35
28.5
GMV-48WL/C-T(U)
208/230V~
60Hz
40
40
33
GMV-60WL/C-T(U)
208/230V~
60Hz
40
40
34.5
Summary of Contents for GMV-24WL/C-T
Page 4: ...GREE DC Inverter Side Discharge VRF for North America 1 PRODUCT...
Page 12: ...GREE DC Inverter Side Discharge VRF for North America 9 CONTROL...
Page 17: ...GREE DC Inverter Side Discharge VRF for North America 14...
Page 18: ...GREE DC Inverter Side Discharge VRF for North America 15 Button Graphics...
Page 65: ...GREE DC Inverter Side Discharge VRF for North America 62 Switchover of Software Languages...
Page 66: ...GREE DC Inverter Side Discharge VRF for North America 63 INSTALLATION...
Page 98: ...GREE DC Inverter Side Discharge VRF for North America 95 MAINTENANCE...
Page 150: ...JF00302320...