GREE DC Inverter Side Discharge VRF
Ⅱ
for North America
120
Removal operation of compressor
Remark: Before removing the compressor, please make sure that there’s no refrigerant inside the pipeline and the
power is disconnected.
Process
Photo
Operation Instruction
7. Connect the
power cord of
compressor well
● Loose screws fixing
the power cord with
screwdriver
● conenct the power
cord well again
Note: When
connecting the power
cord, make marks for
different color power
cords and
corresponding wiring
terminals.
8. Check and
open the upper
cover plate
●Check whether the
pipeline is connected
well
●Check whetehr all
parts and connection
wires are connected
well
●If there’s no
problem after
checking, install front
and rear cover
plates.
Removal operation for 4-way valve
Remark: Before removing the 4-way val
ve, please make sure that there’s no refrigerant inside the pipeline of system
and then power is disconnected.
Process
Photo
Operation Instruction
1.Disconnect
the coil of 4-way
valve from the
4-way valve
●Remove the coil of
4-way valve at first
Summary of Contents for GMV-24WL/C-T
Page 4: ...GREE DC Inverter Side Discharge VRF for North America 1 PRODUCT...
Page 12: ...GREE DC Inverter Side Discharge VRF for North America 9 CONTROL...
Page 17: ...GREE DC Inverter Side Discharge VRF for North America 14...
Page 18: ...GREE DC Inverter Side Discharge VRF for North America 15 Button Graphics...
Page 65: ...GREE DC Inverter Side Discharge VRF for North America 62 Switchover of Software Languages...
Page 66: ...GREE DC Inverter Side Discharge VRF for North America 63 INSTALLATION...
Page 98: ...GREE DC Inverter Side Discharge VRF for North America 95 MAINTENANCE...
Page 150: ...JF00302320...