GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
297
Temperature (°C)
Resistance (kΩ)
Voltage (V)
Temperature (°C)
Resistance (kΩ)
Voltage (V)
45
6.529
2.299
135
0.391
3.216
46
6.278
2.326
136
0.382
3.218
47
6.038
2.353
137
0.372
3.22
48
5.809
2.379
138
0.363
3.222
49
5.589
2.404
139
0.355
3.224
50
5.379
2.429
140
0.346
3.226
51
5.179
2.453
141
0.338
3.227
52
4.986
2.477
142
0.33
3.229
53
4.802
2.5
143
0.322
3.231
54
4.625
2.522
144
0.314
3.232
55
4.456
2.544
145
0.307
3.234
56
4.294
2.566
146
0.299
3.235
57
4.139
2.586
147
0.292
3.237
58
3.99
2.607
148
0.286
3.238
59
3.848
2.626
149
0.279
3.24
60
3.711
2.646
150
0.273
3.241
61
3.579
2.664
151
0.266
3.242
62
3.454
2.682
152
0.261
3.244
63
3.333
2.7
153
0.254
3.245
64
3.217
2.717
154
0.248
3.246
65
3.105
2.734
155
0.243
3.247
66
2.998
2.75
156
0.237
3.249
67
2.898
2.766
157
0.232
3.25
68
2.797
2.781
158
0.227
3.251
69
2.702
2.796
159
0.222
3.252
70
2.611
2.811
160
0.217
3.253
(2)
Voltage list of 20 kΩ pipeline temperature sensors (including temperature sensors for defroster,
sub-cooler, gas/liquid separator, and IDU suction and discharge pipes)
Temperature (°C)
Resistance (kΩ)
Voltage (V)
Temperature (°C)
Resistance (kΩ)
Voltage (V)
-30
361.8
0.173
66
3.998
2.75
-29
339.8
0.183
67
3.861
2.766
-28
319.2
0.195
68
3.729
2.781
-27
300
0.206
69
3.603
2.796
-26
282.2
0.218
70
3.481
2.811
-25
265.5
0.231
71
3.364
2.825
-24
249.9
0.245
72
3.252
2.838
-23
235.3
0.259
73
3.144
2.852
-22
221.6
0.273
74
3.04
2.865
-21
208.9
0.288
75
2.94
2.877
-20
196.9
0.304
76
2.844
2.889
-19
181.4
0.328
77
2.752
2.901
-18
171.4
0.345
78
2.663
2.912
-17
162.1
0.362
79
2.577
2.923
-16
153.3
0.381
80
2.495
2.934
-15
145
0.4
81
2.415
2.944
-14
137.2
0.42
82
2.339
2.954
-13
129.9
0.44
83
2.265
2.964
-12
123
0.462
84
2.194
2.974