![Gree /E-X Service Manual Download Page 204](http://html1.mh-extra.com/html/gree/e-x/e-x_service-manual_2260202204.webp)
GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
200
2.2.4.84
“HC” AC input voltage of drive of inverter fan
Error display:
ODU mainboard will display
Error judgment condition and method:
Check the error code on nixie tube of ODU main control board. If HC is displayed, it indicates AC
input voltage of drive of inverter fan
Possible reason
:
■Fan drive board is abnormal
Troubleshooting:
2.2.4.85
”HH” fan drive DC bus high voltage protection
Error display:
ODU mainboard will display
Error judgment condition and method:
Check the error code on nixie tube of ODU main control board. If HH is displayed, it indicates fan
drive DC bus high voltage protection
Possible reason
:
■Power supply voltage is higher than 460V;
■Fan drive board is abnormal.
Troubleshooting: