GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
190
Troubleshooting:
2.2.4.72
“FJ” Compressor 6 current sensor error
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will
display
Error judgment condition and method:
Sample the AD value of current sensor through detecting circuit and judge the range of AD value; if
the sampled AD value exceeds upper limit and lower limit in 3 seconds continuously, report the error.
Possible reason
:
■Poor contact between circuit sensor and terminal in mainboard interface
■Small board of circuit sensor is abnormal
■Detecting circuit is abnormal