Page 64
Appendix A2: Wilo Yonos PARA RS RKC
A2.2 CIRCULATING PUMP FAULT DIAGNOSIS -
WILO YONOS PARA RS RKC
The indicator LED, located around the circumference of the red control knob can assist in diagnosing and rectifying a fault with the
pump. See the table below:
Table A2-2:
Pump fault diagnosis
LED condition
Meaning
Diagnostic
Cause
Remedy
Green
Pump operating
Pump runs according to the
red knob setting
Normal operation
N/A
Flashes red and green
Pump is operating but
stopped
Pump restarts itself after
fault has disappeared
Undervoltage
Voltage <160V
OR
Overvoltage
Voltage >253V
Check supply voltage is
195V<V<253V
Overheating:
temperature inside motor
too high
Check water and ambient
temperature
Flashes red
Pump not operating
Pump stopped (blocked)
Pump does not restart itself
due to a permanent failure
Replace pump
LED off
No power supply
No voltage to pump control
electronics
Pump is not connected to
power supply
Check cable connection
LED is damaged
Check if pump is running
Electronics are damaged
Replace pump