background image

IO-213D

     2/04

17

• Thirty (30) seconds after the main valve is energized the

circulating air blower will be activated.

• The furnace will remain in operation until the demand for

heat is satisfied.

• Once the demand is satisfied the venter will shut off, and

the circulating air blower will shut off after the field
selectable time off is attained.

• The furnace will remain dormant until the next demand for

heat.

Cooling Mode

• The control checks for an open limit. If an open limit is

detected, the furnace will remain inoperable until the
condition is corrected. During an open limit condition, the
circulating air blower will be energized. The status light
will blink four (4) times.

• A demand for cooling is initiated.
• The condenser contactor will close.
• After approximately five (5) seconds, the circulating air

blower will start on the cooling speed.

• After the room thermostat is satisfied, the condenser

contactor will open.

• The circulating air blower will remain in operation for

approximately sixty (60) seconds.

REMOVING AN EXISTING APPLIANCE

When replacing an existing appliance, the resulting
installation must comply with all local codes, or in the
absence of local codes, to the National Fuel Gas Codes
ANSI Z223.1 and/or CAN/CGA B149 Installation Codes as
well as these installation instructions.

If the installation of this GMNT furnace requires that an
existing appliance be removed from a venting system, which
still serves another gas, fired appliance, this may require
that the existing vent be re-sized. The following steps shall
be performed with each appliance connected to the venting
system placed in operation while any other appliance
connected to the venting system are not in operation;

a. Sealing unused openings in the venting system;
b. Inspect the venting system for proper size and      horizontal

pitch, as required in the National Fuel Gas Code, ANSI
Z223.1 or the CAN/CGA B149 Installation Codes and these
instructions. Determine that there is no blockage or
restriction, leakage, corrosion and other deficiencies,
which could cause an unsafe condition;

c. In so far as practical, close all building doors and windows

and all doors between the space in which the appliance(s)
connected to the venting system are located and other
spaces in the building. Turn on clothes dryers and any
other appliance not connected to the venting system. Turn
on any exhaust fans such as range hoods and bathroom
exhausts, so they shall operate at their maximum speed.
DO NOT operate a summer exhaust fan (whole house
fan). Close fireplace dampers;

d. Follow lighting instructions. Place the appliance being

inspected in operation. Adjust the thermostat so the
appliance shall operate continuously;

e. Test for draft hood equipped appliance spillage at the relief

opening after five (5) minutes of burner operation. Use the
flame of a match or candle;

f. After it has been determined that each appliance connected

to the venting system properly vents when tested as
outlined above, return all doors, windows, exhaust fans,
fireplace dampers and any other gas-burning appliance
back to their previous condition of use;

g. If improper venting is observed during any of the above

tests, the venting system must be corrected.

INSPECTING AND CLEANING THE HEAT EXCHANGER

CAUTION

LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN
SERVICING CONTROLS.  WIRING ERRORS CAN CAUSE
DANGEROUS AND IMPROPER OPERATION. VERIFY
PROPER OPERATION AFTER SERVICING.

It is the obligation of the installer to advise the user to have
the furnace inspected and cleaned annually. To clean the
heat exchanger, perform the following:

• Adjust the room thermostat to its lowest setting.
• Turn off the gas and electric supply to the furnace.
• Remove the control access door.
• Open the gas supply union.
• Disconnect the gas supply line attached to the gas valve.
• Remove the wires connected to the gas valve.
• Remove the burner box assembly. Care must be exercised

to avoid damage to the igniter.

• Inshot burners should not require cleaning. However, if

they exhibit signs of corrosion they can be cleaned by
brushing with a stiff wire brush.

• Remove the vent from the furnace venter blower.
• Remove the venter blower and collector box.
• With a stiff wire brush on a flexible handle, remove any

loose scale from the heat exchanger at both the flue and
burner openings.

• Use a 1/2" diameter brush to remove any deposits in the

secondary heat exchanger.

• With a vacuum, remove any loose scale dislodged and

any additional debris found in the heat exchanger.

• Visually inspect the heat exchanger cells for any cracks or

openings using a bright light.

If any failures are discovered, it is important to disable
the furnace and notify the user to ensure that it remains
inoperable until repairs are implemented.

• Reassemble the furnace in the reverse order. 

Note:

 No

additional screws or wires are supplied with this product.
All components must be reassembled to avoid an unsafe
condition.

• Reconnect gas supply and check for leaks using a soap

solution. If a flexible gas line is used, examine it for cracks
or weakness. Replace if necessary.

• Restore electrical power.
• Follow the lighting instructions to place the furnace into

operation.

Note:

 It is important to use a pipe joint compound that is

resistant to the effects of L.P. gas.

Summary of Contents for GMNT

Page 1: ...SYSTEMAND ANY GAS CONTROL THAT HAS BEEN UNDER WATER WARNING THIS FURNACE IS DESIGN CERTIFIED FOR INSTALLATION IN BUILDINGS CONSTRUCTED ON SITE ONLY C US INSTALLATION OPERATING INSTRUCTIONS for GMNT C...

Page 2: ...ary coil Collector Box ELECTRICAL CONTROLS Control board Auxiliary main limit switch Roll out switch Transformer Door interlock switch Air pressure switch Induced draft blower BURNER ASSEMBLY Burners...

Page 3: ...INTAINED AND MONITORED IN THE EVENT THAT THE BUILDING MAY BE EXPOSED TO FREEZING TEMPERATURES AND WILL BE VACANT ALL WATER BEARING PIPES SHOULD BE DRAINED THE BUILDING SHOULD BE PROPERLY WINTERIZED AN...

Page 4: ...BUSTIBLE MATERIAL MUST NOT BE PLACED ON OR AGAINST THE FURNACE CABINET THE AREA AROUND THE FURNACE MUST BE KEPT CLEAR AND FREE OF ALL COMBUSTIBLE MATERIAL INCLUDING GASOLINE AND OTHER FLAMMABLE VAPORS...

Page 5: ...Two permanent openings communicating directly with the outdoors via horizontal ducts shall be sized to be a minimum of 1 square inch per 4 000 Btu hr or two permanent openings communicating directly...

Page 6: ...k for blockage of the condensate disposal system Hoses may be disconnected to determine that proper flow is maintained Should an obstruction be observed it can be dislodged by forcing a stream of wate...

Page 7: ...air may be obtained from the bottom of the unit providing there is at least 4 of unobstructed space It is recommended that the plug is removed and the combustion air supply is obtained from both open...

Page 8: ...AL REQUIREMENT THE COMBUSTION PRODUCTS IN THE FLUE GASES WILL CONDENSE THE CONDENSATE MAY FREEZE ON THE EXTERIOR WALL AND SURROUNDING SURFACES SOME DISCOLORATION OR ETCHING IS TO BE EXPECTED When sele...

Page 9: ...IO 213D 2 04 9 DRAIN CONNECTIONS HORIZONTAL RIGHT SIDE HORIZONTAL LEFT SIDE AIR FLOW AIR FLOW...

Page 10: ...IO 213D 2 04 10 DRAINCONNECTIONS UPFLOW LEFT DOWNFLOW LEFT SIDE DOWNFLOW RIGHT SIDE UPFLOW RIGHT SIDE...

Page 11: ...ip e o f d iffe re n t d ia m e te rs a n d le n g th in ft 3 h r w ith a p re s s u re d ro p o f 0 3 W C a n d a s p e c ific g ra v ity o f 0 6 0 n a tu ra l g a s After the length of pipe has bee...

Page 12: ...he furnace for electrical connection The junction box may be moved to either side The entry holes for supply and low voltage control wires are for use with electrical connectors All electrical wiring...

Page 13: ...ES RATING PLATE INPUT 1000 Example Corrected input for a 100 000 Btu hr appliance installed at an altitude of 6 000 ft utilizing natural gas with a heating value of 1 000 But ft3 is determined by Corr...

Page 14: ...d 3 Attach a 5 16 inch hose and manometer to the outlet pressure boss of the valve see fig 1 Hose should overlap boss 3 8 inch 4 Turn on system power and set thermostat to call for heat 5 Using a leak...

Page 15: ...function contact a qualified service person to determine the cause of function before resetting To reset this switch press the button on top of the switch after the furnace has cooled To test the oper...

Page 16: ...overheating due to an accumulation of dust or dirt on the windings and motor casing As suggested elsewhere in these instructions the air filters are to be kept clean Dirty filters will restrict the a...

Page 17: ...replace dampers d Follow lighting instructions Place the appliance being inspected in operation Adjust the thermostat so the appliance shall operate continuously e Test for draft hood equipped applian...

Page 18: ...any part of a qualified service technician to inspect has been under water Immediately call D Do not use this appliance if any part tools If the gas control switch or knob control switch or knob Neve...

Page 19: ...GAS VALVE HSI HOT SURFACE IGNITOR IDBR2 IDBR1 INDOOR BLOWER HEAT RELAY PV POWER VENTOR FS FLAME SENSOR PS LS DS IDB GV FS HSI SO W COOL HEAT M1 M2 HSI IND NEUTRALS PRI TRANS W G R L2 W W R LIMIT PSI P...

Page 20: ...t causes of product failure They are simple to service and forgiving to operate We use quality materials and components Finally every unit is run tested before it leaves the factory That s why we know...

Reviews: