background image

IO-213D

     2/04

13

Blower Time Selection

The blower “OFF” timing is field selectable. See below for
the method of changing these times.

BLOWER OFF

TERMINAL

90

120

150

FACTORY SETTING

150 SEC.

OPTIONAL SETTINGS

120 SEC. 

    90 SEC.

90

120

150

90

120

150

Twinning

• The twin feature allows two furnaces to be connected to a

single control circuit.

• A common ground 

must

 be provided between the units to

be connected.

• The power supply 

must

 be obtained from the same buss

bar in the circuit breaker box (each furnace 

must 

have a

grounded, dedicated circuit).

• The control board 

must

 be produced by the same

manufacturer.

• It is recommended that common ductwork be used.
• A wire 

must

 run between the “TWIN” terminals. These

terminals are 3/16".

RATING THE FURNACE

This furnace is shipped from the factory equipped for use
with natural gas. The instructions are for use with natural
gas at altitudes up to 2,000 feet, using a heating value of
1,000 Btu/hr. Should this appliance be converted to L.P.,
refer to the instructions included in the factory authorized
L.P. Conversion Kit 

(LPT-01)

. If for use at altitudes in excess

of 2,000 feet refer to the instructions included in the factory
authorized High Altitude Kit

 (HA-02).

It is important to check and adjust the input rate of the
furnace to prevent an overfiring situation. Overfiring can cause
premature heat exchanger failure. The input is controlled
by the supply pressure, orifice size, manifold pressure and
heating (calorific) value of the gas.

The supply pressure must be measured with this and all
other gas burning appliances in operation. The supply
pressure must be adjusted to the pressure range stated on
the series and rating plate. Applications for altitudes in
excess of 2,000 feet require an orifice change. The orifices
must be selected using the table below. 

The furnace derate

is 4% for each 1,000 feet

 

above sea level

. This table is

based upon a heating value of approximately 1,000 Btu/ft

3

.

   ALTITUDE

NAT. GAS ORIFICE SIZE

      0 – 1,999

#45

2,000 – 2,999

#46

3,000 – 3,999

#47

4,000 – 4,999

#47

5,000 – 5,999

#47

6,000 – 7,000

#48

The input to the furnace must be checked AFTER reorificing.
For altitudes above 7,000 feet refer to appropriate section of
the National Fuel Gas Code, ANSI Z223.1. To calculate the
input of the furnace for installations in altitudes over 2,000
feet, use the following formula;

CORRECTED INPUT = SERIES & RATING PLATE INPUT -
(ALTITUDE X .04) X SERIES & RATING PLATE INPUT /
1000

Example:

Corrected input for a 100,000 Btu/hr. appliance installed at
an altitude of 6.000 ft. utilizing natural gas with a heating
value of 1,000 But/ft

3

 is determined by-

Corrected Input =  100,000 - (6,000 X .04) X (100,000 / 1,000)
Corrected Input =  100,000 - (240 X 100)
Corrected Input =  100,000 - 24,000
Corrected Input =  76,000

Using the orifices sized as shown in the table for 6,000 feet
(#48), a meter time of 48.0 seconds is measured. The actual
firing rate of the furnace is

Input  =   1,000 (heating value of the gas) X 3600 (constant) /
               48.0 (meter time for 1 ft

of gas)

Input  =   3,600,000 / 48.0
Input  =   76,000 Btu/hr

In Canada, the series and rating plate input for the furnace
apply to installations up to 2,000 feet (610m) above sea
level. Kit HA-02 for natural and L.P. gases is required to
convert furnaces from elevations of 2,000 to 4,500 feet (610m
to 1,370m). Canadian certification applies to the installations
of up to 4,500 feet above sea level. Installations above 4,500
feet are subject to acceptance by the local authorities having
jurisdiction.

WARNING

BEFORE ATTEMPTING ANY SERVICE OR ADJUSTMENTS
- ENSURE THAT THE GAS AND ELECTRICAL SUPPLIES
ARE  “OFF”.

TIMING THE GAS METER

Use the following method to determine the firing rate of the
furnace. The supply pressure tap should be located on the
field-installed piping or gas shut-off valve. The manifold
pressure tap is located on the combination gas valve in the
furnace and labeled “OUTLET PRESSURE TAP”.

• Install a manometer graduated in tenths of an inch of water

column on the supply pressure tap of the gas supply pipe.

• Remove plug at the “Manifold” pressure tap on the gas

valve and install a second manometer.

• Determine the size of gas meter used.
• Shut off all other gas fired appliances with the exception of

the pilots.

• Place furnace in operation.
• Check the supply pressure as shown on the series and

rating plate.

• After 15 minutes of operation, time the meter with a

stopwatch for 2 revolutions & divide by 2.

• Use the appropriate column in the following table to

determine the furnace input.

• If necessary, adjust the manifold pressure at the gas valve

by removing the regulator cap and turning the adjustment
screw clockwise (

P

) to raise the pressure and

counterclockwise (

Q

) to reduce the pressure. The manifold

pressure must be between 3.2" W.C. and 3.8" W.C. for
natural gas and 9.5"W.C. and 10.5" W.C. for L.P. (a field
conversion is necessary for L.P.). The inability to maintain
the proper pressure range will require reorificing. After
replacing the orifices, repeat the above steps to insure
that the furnace input is adjusted properly.

Summary of Contents for GMNT

Page 1: ...SYSTEMAND ANY GAS CONTROL THAT HAS BEEN UNDER WATER WARNING THIS FURNACE IS DESIGN CERTIFIED FOR INSTALLATION IN BUILDINGS CONSTRUCTED ON SITE ONLY C US INSTALLATION OPERATING INSTRUCTIONS for GMNT C...

Page 2: ...ary coil Collector Box ELECTRICAL CONTROLS Control board Auxiliary main limit switch Roll out switch Transformer Door interlock switch Air pressure switch Induced draft blower BURNER ASSEMBLY Burners...

Page 3: ...INTAINED AND MONITORED IN THE EVENT THAT THE BUILDING MAY BE EXPOSED TO FREEZING TEMPERATURES AND WILL BE VACANT ALL WATER BEARING PIPES SHOULD BE DRAINED THE BUILDING SHOULD BE PROPERLY WINTERIZED AN...

Page 4: ...BUSTIBLE MATERIAL MUST NOT BE PLACED ON OR AGAINST THE FURNACE CABINET THE AREA AROUND THE FURNACE MUST BE KEPT CLEAR AND FREE OF ALL COMBUSTIBLE MATERIAL INCLUDING GASOLINE AND OTHER FLAMMABLE VAPORS...

Page 5: ...Two permanent openings communicating directly with the outdoors via horizontal ducts shall be sized to be a minimum of 1 square inch per 4 000 Btu hr or two permanent openings communicating directly...

Page 6: ...k for blockage of the condensate disposal system Hoses may be disconnected to determine that proper flow is maintained Should an obstruction be observed it can be dislodged by forcing a stream of wate...

Page 7: ...air may be obtained from the bottom of the unit providing there is at least 4 of unobstructed space It is recommended that the plug is removed and the combustion air supply is obtained from both open...

Page 8: ...AL REQUIREMENT THE COMBUSTION PRODUCTS IN THE FLUE GASES WILL CONDENSE THE CONDENSATE MAY FREEZE ON THE EXTERIOR WALL AND SURROUNDING SURFACES SOME DISCOLORATION OR ETCHING IS TO BE EXPECTED When sele...

Page 9: ...IO 213D 2 04 9 DRAIN CONNECTIONS HORIZONTAL RIGHT SIDE HORIZONTAL LEFT SIDE AIR FLOW AIR FLOW...

Page 10: ...IO 213D 2 04 10 DRAINCONNECTIONS UPFLOW LEFT DOWNFLOW LEFT SIDE DOWNFLOW RIGHT SIDE UPFLOW RIGHT SIDE...

Page 11: ...ip e o f d iffe re n t d ia m e te rs a n d le n g th in ft 3 h r w ith a p re s s u re d ro p o f 0 3 W C a n d a s p e c ific g ra v ity o f 0 6 0 n a tu ra l g a s After the length of pipe has bee...

Page 12: ...he furnace for electrical connection The junction box may be moved to either side The entry holes for supply and low voltage control wires are for use with electrical connectors All electrical wiring...

Page 13: ...ES RATING PLATE INPUT 1000 Example Corrected input for a 100 000 Btu hr appliance installed at an altitude of 6 000 ft utilizing natural gas with a heating value of 1 000 But ft3 is determined by Corr...

Page 14: ...d 3 Attach a 5 16 inch hose and manometer to the outlet pressure boss of the valve see fig 1 Hose should overlap boss 3 8 inch 4 Turn on system power and set thermostat to call for heat 5 Using a leak...

Page 15: ...function contact a qualified service person to determine the cause of function before resetting To reset this switch press the button on top of the switch after the furnace has cooled To test the oper...

Page 16: ...overheating due to an accumulation of dust or dirt on the windings and motor casing As suggested elsewhere in these instructions the air filters are to be kept clean Dirty filters will restrict the a...

Page 17: ...replace dampers d Follow lighting instructions Place the appliance being inspected in operation Adjust the thermostat so the appliance shall operate continuously e Test for draft hood equipped applian...

Page 18: ...any part of a qualified service technician to inspect has been under water Immediately call D Do not use this appliance if any part tools If the gas control switch or knob control switch or knob Neve...

Page 19: ...GAS VALVE HSI HOT SURFACE IGNITOR IDBR2 IDBR1 INDOOR BLOWER HEAT RELAY PV POWER VENTOR FS FLAME SENSOR PS LS DS IDB GV FS HSI SO W COOL HEAT M1 M2 HSI IND NEUTRALS PRI TRANS W G R L2 W W R LIMIT PSI P...

Page 20: ...t causes of product failure They are simple to service and forgiving to operate We use quality materials and components Finally every unit is run tested before it leaves the factory That s why we know...

Reviews: