background image

IO-213D

     2/04

11

GAS PIPING  & GAS PIPE CAPACITY TABLE

Check the rating plate to make certain that the gas supplied
is compatible with the unit requirements. Care should be
taken after the installation of this appliance that the gas
control valve is not subjected to high gas supply line
pressure. In making connections, avoid strains as they may
cause noise and damage the controls. Always use a back-
up wrench when tightening the gas supply pipe to the gas
control valve. Check for leaks in the gas supply using soap
bubbles or other approved methods.

NEVER USE AN OPEN FLAME TO CHECK FOR GAS
LEAKS.  THIS PRACTICE MAY CAUSE A FIRE,
EXPLOSION, BODILY HARM OR PROPERTY DAMAGE.

Pipe joint compound must be resistant to the action of L.P.
gas. When connecting the gas service to the furnace, a
ground joint union and manual shutoff must be installed
exterior to the furnace cabinet and located in the same room
so the control assembly may be easily removed.

A 1/8" NPT plug on the supply pipe near the manual valve
for the purpose of making pressure measurement should
also be installed. The valve should be readily accessible for
turning on or off. A capped sediment trap, sometimes called
a drip leg, must be installed in the gas supply pipe as close
to the furnace as possible. The sediment trap must
incorporate a change of gas flow direction.

Refer to local codes or the previously mentioned publications
for proper location and size of the manual shutoff and
sediment trap lengths.

The gas pipe must be sized to eliminate undue pressure
drop. See pipe capacity table or consult your local utility.
Both the supply and manifold pressure must be measured
with the furnace running using the field supplied pressure
tap near the manual shut-off valve and the pressure adjusted
if necessary.

All gas piping must conform to local codes, or in the absence
of local codes, to the National Fuel Gas Code ANSI Z223.1
and / or CAN/CGA B149 Installation Codes.

Note: 

Copper tubing must not be used for natural gas

installations where more than .3 grains of hydrogen sulfide
per 100 standard cubic feet of gas is present. (If the
quantities of hydrogen sulfide cannot be verified, do not use
copper).

FOR INSTALLATIONS IN THE COMMONWEALTH OF
MASSACHUSETTS SEE FUEL GAS AND PLUMBING
CODE 248 CMR: APPENDIX C.

P ip e  

S iz e *

½

¾

1

1   ¼

1   ½

1 0

1 3 2

2 7 8

5 2 0

1 0 5 0

1 6 0 0

2 0

9 2

1 9 0

3 5 0

7 3 0

1 1 0 0

L e n g th

3 0

7 3

1 5 2

2 8 5

5 9 0

8 9 0

o f

4 0

6 3

1 3 0

2 4 5

5 0 0

7 6 0

P ip e

5 0

5 6

1 1 5

2 1 5

4 4 0

6 7 0

in  F e e t

6 0

5 0

1 0 5

1 9 5

4 0 0

6 1 0

7 0

4 6

9 6

1 8 0

3 7 0

5 6 0

8 0

4 3

9 0

1 7 0

3 5 0

5 3 0

* N o m in a l  s iz e   o f  iro n   p ip e   in   in c h e s .

C a p a c ity   o f  g a s   p ip e   o f  d iffe re n t   d ia m e te rs   a n d   le n g th   in  

ft

3

/ h r.  w ith   a   p re s s u re   d ro p   o f  0 . 3 "   W .C .  a n d   a   s p e c ific  

g ra v it y   o f   0 . 6 0   (n a t u ra l  g a s ).

After the length of pipe has been determined, select the
pipe size, which will provide the minimum cubic feet per

hour of gas flow for the required input of the appliance. In
the case where more than one appliance utilizes the same
supply pipe be sure to consider the sum of all appliances.
The cubic feet of gas required for the appliances should be
determined using the following formula;

Cubic feet of           Gas input of appliance (BTU/hr.)

gas required            Heating value of gas (BTU/hr.)

The gas input of the appliance is marked on the specification
plate. The heating value of the gas may be determined by
contacting the gas utility or gas supplier.

CAUTION

IF THE LOCAL UTILITY PERMITS THE USE OF A FLEXIBLE
GAS CONNECTOR - 

ALWAYS USE A NEW FLEXIBLE

CONNECTOR

.  

DO NOT

 USE FLEXIBLE GAS LINES THAT

HAVE SERVICED ANOTHER APPLIANCE.  AFTER A PERIOD
OF TIME THESE LINES MAY BECOME BRITTLE AND CAN
DEVELOP LEAKS.  THE CONNECTIONS TO A FLEXIBLE
GAS LINE MUST BE MADE OUTSIDE OF THE FURNACE
CABINET.

CIRCULATING AIR SUPPLY AND RETURN AIR

The circulating air supply may be taken from; 1) Outside
the building, 2) return ducts from several rooms, 3) central
return, 4) any combination of the above.

When a cooling coil is not installed it is recommended that
the supply duct have an access panel so the heat exchanger
can be viewed. This panel shall be of sufficient size to permit
the entrance of a light or probe to assist in the observation
of the heat exchanger integrity or sampling the air stream.
It should be sealed to prevent air leakage during normal
operation.

Return air from one dwelling shall not be discharged into
another dwelling through the heating system.

There shall be a positive separation between combustion
air and return air.

Do not obtain return air from a hazardous or insanitary
location or a refrigeration machinery room or any room or
space having any fuel-burning appliances therein.

CAUTION

DO NOT TAKE RETURN AIR FROM BATHROOMS,
KITCHENS, FURNACE ROOMS, GARAGES, UTILITY/
LAUNDRY ROOMS OR COLD AREAS.  IF OUTSIDE AIR IS
UTILIZED, IT SHOULD NOT BE TAKEN FROM WITHIN 10
FEET OF AN APPLIANCE VENT OUTLET, A VENT OPENING
OR A PLUMBING DRAINAGE SYSTEM, OR THE DISCHARGE
FROM AN EXHAUST SYSTEM UNLESS THE OUTLET IS
THREE (3) FEET ABOVE THE OUTSIDE AIR INLET.  DO
NOT TAKE RETURN AIR FROM AN AREA WHERE IT CAN
PICK-UP OBJECTIONABLE ODORS, FUMES, OR
FLAMMABLE VAPORS.

Note:

 When a combination of outdoor and indoor air is

utilized the system should be designed and adjusted such
that the temperature reaching the appliance will not drop
below 50

o

 F during heating operation. This will minimize the

possibility of condensate forming inside the heat exchanger.
When this type of system is utilized the volume of air must
not be reduced.

=

Summary of Contents for GMNT

Page 1: ...SYSTEMAND ANY GAS CONTROL THAT HAS BEEN UNDER WATER WARNING THIS FURNACE IS DESIGN CERTIFIED FOR INSTALLATION IN BUILDINGS CONSTRUCTED ON SITE ONLY C US INSTALLATION OPERATING INSTRUCTIONS for GMNT C...

Page 2: ...ary coil Collector Box ELECTRICAL CONTROLS Control board Auxiliary main limit switch Roll out switch Transformer Door interlock switch Air pressure switch Induced draft blower BURNER ASSEMBLY Burners...

Page 3: ...INTAINED AND MONITORED IN THE EVENT THAT THE BUILDING MAY BE EXPOSED TO FREEZING TEMPERATURES AND WILL BE VACANT ALL WATER BEARING PIPES SHOULD BE DRAINED THE BUILDING SHOULD BE PROPERLY WINTERIZED AN...

Page 4: ...BUSTIBLE MATERIAL MUST NOT BE PLACED ON OR AGAINST THE FURNACE CABINET THE AREA AROUND THE FURNACE MUST BE KEPT CLEAR AND FREE OF ALL COMBUSTIBLE MATERIAL INCLUDING GASOLINE AND OTHER FLAMMABLE VAPORS...

Page 5: ...Two permanent openings communicating directly with the outdoors via horizontal ducts shall be sized to be a minimum of 1 square inch per 4 000 Btu hr or two permanent openings communicating directly...

Page 6: ...k for blockage of the condensate disposal system Hoses may be disconnected to determine that proper flow is maintained Should an obstruction be observed it can be dislodged by forcing a stream of wate...

Page 7: ...air may be obtained from the bottom of the unit providing there is at least 4 of unobstructed space It is recommended that the plug is removed and the combustion air supply is obtained from both open...

Page 8: ...AL REQUIREMENT THE COMBUSTION PRODUCTS IN THE FLUE GASES WILL CONDENSE THE CONDENSATE MAY FREEZE ON THE EXTERIOR WALL AND SURROUNDING SURFACES SOME DISCOLORATION OR ETCHING IS TO BE EXPECTED When sele...

Page 9: ...IO 213D 2 04 9 DRAIN CONNECTIONS HORIZONTAL RIGHT SIDE HORIZONTAL LEFT SIDE AIR FLOW AIR FLOW...

Page 10: ...IO 213D 2 04 10 DRAINCONNECTIONS UPFLOW LEFT DOWNFLOW LEFT SIDE DOWNFLOW RIGHT SIDE UPFLOW RIGHT SIDE...

Page 11: ...ip e o f d iffe re n t d ia m e te rs a n d le n g th in ft 3 h r w ith a p re s s u re d ro p o f 0 3 W C a n d a s p e c ific g ra v ity o f 0 6 0 n a tu ra l g a s After the length of pipe has bee...

Page 12: ...he furnace for electrical connection The junction box may be moved to either side The entry holes for supply and low voltage control wires are for use with electrical connectors All electrical wiring...

Page 13: ...ES RATING PLATE INPUT 1000 Example Corrected input for a 100 000 Btu hr appliance installed at an altitude of 6 000 ft utilizing natural gas with a heating value of 1 000 But ft3 is determined by Corr...

Page 14: ...d 3 Attach a 5 16 inch hose and manometer to the outlet pressure boss of the valve see fig 1 Hose should overlap boss 3 8 inch 4 Turn on system power and set thermostat to call for heat 5 Using a leak...

Page 15: ...function contact a qualified service person to determine the cause of function before resetting To reset this switch press the button on top of the switch after the furnace has cooled To test the oper...

Page 16: ...overheating due to an accumulation of dust or dirt on the windings and motor casing As suggested elsewhere in these instructions the air filters are to be kept clean Dirty filters will restrict the a...

Page 17: ...replace dampers d Follow lighting instructions Place the appliance being inspected in operation Adjust the thermostat so the appliance shall operate continuously e Test for draft hood equipped applian...

Page 18: ...any part of a qualified service technician to inspect has been under water Immediately call D Do not use this appliance if any part tools If the gas control switch or knob control switch or knob Neve...

Page 19: ...GAS VALVE HSI HOT SURFACE IGNITOR IDBR2 IDBR1 INDOOR BLOWER HEAT RELAY PV POWER VENTOR FS FLAME SENSOR PS LS DS IDB GV FS HSI SO W COOL HEAT M1 M2 HSI IND NEUTRALS PRI TRANS W G R L2 W W R LIMIT PSI P...

Page 20: ...t causes of product failure They are simple to service and forgiving to operate We use quality materials and components Finally every unit is run tested before it leaves the factory That s why we know...

Reviews: