background image

IO-213D

2/04

12

Plenum chambers and air ducts must be installed in
accordance with the Standard for the Installation of Air
Conditioning and Ventilating Systems, NFPA #90A, or the
Standard for the Installation of Warm Air Heating and Air
Conditioning Systems, NFPA # 90B.

If installed in parallel with a cooling unit the damper or other
means used to control the flow of air must be adequate to
prevent chilled air from entering the furnace, and if manually
operated must be equipped with means to prevent operation
of the other unit unless the damper is in the full heat or cool
position.

NOTE:

 UPON INITIAL START-UP SOME SMOKE OR AN ODOR

MAY BE PRESENT. THIS IS NORMAL AND SHOULD
DISAPPEAR IN A SHORT AMOUNT OF TIME.

 

IT IS

RECOMMENDED THAT WINDOWS AND DOORS BE OPENED
UPON INITIAL START-UP TO VENT THIS 

NON-TOXIC

 SMOKE.

One of the most common causes of problems, including
premature heat exchanger failure, in a forced air heating
system is insufficient return air. The return air connections
to the furnace should be approximately equal to the area of
warm air discharge. Consult local codes for specific
requirements.

All return ducts must be adequately secured to the furnace
and sealed airtight. All other ductwork must be secured with
approved connections and sealed airtight.

When the furnace is mounted on a platform it must be sealed
air tight between the furnace and the return ductwork. The
floor or platform must provide sound physical support for
the furnace without cracks, gaps, sagging, etc. around the
base as to provide an airtight seal between the support and
the base.

Install the return air to terminate through the base under the
furnace. For installations where return air ducts cannot be
run under the floor, the return air supply may be taken from
the side(s).

Embosses are provided on the sides of the furnace for use
as a template for the ductwork connection.

Where the maximum required airflow is 

1800 c.f.m.

 or

greater, the bottom or both sides must be utilized for return
air supply. Never use the rear of the furnace for the return
connection unless it is for conditions where additional return
air ducts are desired.

ELECTRICAL SUPPLY CONNECTIONS

The electrical requirements are 115Volts, 60 Hz., 1 Ph. A
separate supply line with a current overload device and a
manual switch, where required, must be installed. Type “T”
wire or equivalent with a minimum rating of 95

o

F (35

o

C)

temperature rise must be run directly from the main power
supply. Use copper conductors only.

Holes are provided on both sides of the furnace for electrical
connection. The junction box may be moved to either side.
The entry holes for supply and low voltage control wires are
for use with ½” electrical connectors.

All electrical wiring entering the furnace must be secured to
the casing with proper methods of strain relief. Solderless
connectors may be used to connect wires inside the junction
box for supply wires.

It is recommended that a means of shutting off the power
be within sight of the furnace.

INSTALLATION OF THE ELECTRICAL SUPPLY MUST BE IN
ACCORDANCE WITH LOCAL CODES.  IN THE ABSENCE
OF LOCAL CODES REFER TO THE NATIONAL
ELECTRICAL CODE ANSI/NFPA NO. 7 (LATEST EDITION),
WHICH CAN BE OBTAINED FROM THE NATIONAL FIRE
PROTECTION ASSOCIATION, BATTERYMARCH PARK,
QUINCY, MA 02269. IN CANADA REFER TO THE LATEST
EDITION OF THE CANADIAN ELECTRICAL CODE C22.1
PART I.

CONTROL VOLTAGE CONNECTIONS

Thermostat Installation

Install the thermostat in accordance with the instructions
accompanying the thermostat. Connect the thermostat
wiring to the thermostat terminal block on the furnace control
board.  The thermostat wiring should be a minimum of 18
gauge.  Adhere to recommended color code to facilitate
future troubleshooting.

The thermostat should be located near the return air grille
or opening. It should be approximately 5 feet from the floor
level. Never locate the thermostat where it will be influenced
by heat generated by hot water pipes, lamps, televisions,
direct sunlight, supply air registers, etc.

Interconnecting wiring must be secured and protected from
damage or disconnection. The use of solderless connectors
or equivalent is recommended. The low voltage control wiring
exiting the furnace is labeled “thermostat wiring”.

Setting The Heat Anticipator

Following the instructions accompanying the thermostat for
proper adjustment of the anticipator.

FEATURES

The integrated control board in this furnace has terminals
provided for added features. These features are a 115v.
Humidifier, a 24v. Humidifier, an Electronic Air Cleaner, Blower
“OFF” Timing and Twinning with another furnace.

115 Volt Humidifier

The “115v HUM” terminal is located on the high voltage side
of the board. It is covered with a terminal protector.  See
wiring below.

24 Volt Humidifier

The “HUM” lug for the operation of a 24-volt humidifier is
located in the vicinity of the thermostat connections. See
wiring.

 

HUM

IGNITION CONTROL

FIELD SUPPLIED
HUMIDISTAT

HUMIDIFIER

LINE

NEUTRAL

Electronic Air Cleaner

The E.A.C. terminal is located near the blower speed
connections and is covered with a terminal protector. This
option should be wired in conjunction with the electronic air
cleaner. This feature assures the indoor blower fan is
energized when there is a demand for air cleaner.

Summary of Contents for GMNT

Page 1: ...SYSTEMAND ANY GAS CONTROL THAT HAS BEEN UNDER WATER WARNING THIS FURNACE IS DESIGN CERTIFIED FOR INSTALLATION IN BUILDINGS CONSTRUCTED ON SITE ONLY C US INSTALLATION OPERATING INSTRUCTIONS for GMNT C...

Page 2: ...ary coil Collector Box ELECTRICAL CONTROLS Control board Auxiliary main limit switch Roll out switch Transformer Door interlock switch Air pressure switch Induced draft blower BURNER ASSEMBLY Burners...

Page 3: ...INTAINED AND MONITORED IN THE EVENT THAT THE BUILDING MAY BE EXPOSED TO FREEZING TEMPERATURES AND WILL BE VACANT ALL WATER BEARING PIPES SHOULD BE DRAINED THE BUILDING SHOULD BE PROPERLY WINTERIZED AN...

Page 4: ...BUSTIBLE MATERIAL MUST NOT BE PLACED ON OR AGAINST THE FURNACE CABINET THE AREA AROUND THE FURNACE MUST BE KEPT CLEAR AND FREE OF ALL COMBUSTIBLE MATERIAL INCLUDING GASOLINE AND OTHER FLAMMABLE VAPORS...

Page 5: ...Two permanent openings communicating directly with the outdoors via horizontal ducts shall be sized to be a minimum of 1 square inch per 4 000 Btu hr or two permanent openings communicating directly...

Page 6: ...k for blockage of the condensate disposal system Hoses may be disconnected to determine that proper flow is maintained Should an obstruction be observed it can be dislodged by forcing a stream of wate...

Page 7: ...air may be obtained from the bottom of the unit providing there is at least 4 of unobstructed space It is recommended that the plug is removed and the combustion air supply is obtained from both open...

Page 8: ...AL REQUIREMENT THE COMBUSTION PRODUCTS IN THE FLUE GASES WILL CONDENSE THE CONDENSATE MAY FREEZE ON THE EXTERIOR WALL AND SURROUNDING SURFACES SOME DISCOLORATION OR ETCHING IS TO BE EXPECTED When sele...

Page 9: ...IO 213D 2 04 9 DRAIN CONNECTIONS HORIZONTAL RIGHT SIDE HORIZONTAL LEFT SIDE AIR FLOW AIR FLOW...

Page 10: ...IO 213D 2 04 10 DRAINCONNECTIONS UPFLOW LEFT DOWNFLOW LEFT SIDE DOWNFLOW RIGHT SIDE UPFLOW RIGHT SIDE...

Page 11: ...ip e o f d iffe re n t d ia m e te rs a n d le n g th in ft 3 h r w ith a p re s s u re d ro p o f 0 3 W C a n d a s p e c ific g ra v ity o f 0 6 0 n a tu ra l g a s After the length of pipe has bee...

Page 12: ...he furnace for electrical connection The junction box may be moved to either side The entry holes for supply and low voltage control wires are for use with electrical connectors All electrical wiring...

Page 13: ...ES RATING PLATE INPUT 1000 Example Corrected input for a 100 000 Btu hr appliance installed at an altitude of 6 000 ft utilizing natural gas with a heating value of 1 000 But ft3 is determined by Corr...

Page 14: ...d 3 Attach a 5 16 inch hose and manometer to the outlet pressure boss of the valve see fig 1 Hose should overlap boss 3 8 inch 4 Turn on system power and set thermostat to call for heat 5 Using a leak...

Page 15: ...function contact a qualified service person to determine the cause of function before resetting To reset this switch press the button on top of the switch after the furnace has cooled To test the oper...

Page 16: ...overheating due to an accumulation of dust or dirt on the windings and motor casing As suggested elsewhere in these instructions the air filters are to be kept clean Dirty filters will restrict the a...

Page 17: ...replace dampers d Follow lighting instructions Place the appliance being inspected in operation Adjust the thermostat so the appliance shall operate continuously e Test for draft hood equipped applian...

Page 18: ...any part of a qualified service technician to inspect has been under water Immediately call D Do not use this appliance if any part tools If the gas control switch or knob control switch or knob Neve...

Page 19: ...GAS VALVE HSI HOT SURFACE IGNITOR IDBR2 IDBR1 INDOOR BLOWER HEAT RELAY PV POWER VENTOR FS FLAME SENSOR PS LS DS IDB GV FS HSI SO W COOL HEAT M1 M2 HSI IND NEUTRALS PRI TRANS W G R L2 W W R LIMIT PSI P...

Page 20: ...t causes of product failure They are simple to service and forgiving to operate We use quality materials and components Finally every unit is run tested before it leaves the factory That s why we know...

Reviews: