Goodman CPLE090 Installation & Operating Instructions Manual Download Page 9

9

For installation greater than 25’ of line set, indoor unit airflow,
condensing unit location and number of tubing fittings will have
an impact on final unit charge amount. Start with half of the 25’
line set charge and proceed.

Turn the electrical power on, and let the system run.  Wait for the
refrigerant pressures to stabilize.

EXPANSION VALVE INDOOR COILS:

NOTE:  

EXPANSION VALVE BULB, MUST BE IN PLACE ON

SUCTION LINE & INSULATED.

Outdoor Temperature Over 60

o

F. 

 When the outdoor temperature

is above 60

°

F, the system is to be charged with the room thermostat

set in the “Cooling” mode and the fan operating in the “Auto”
position.

Outdoor Temperature Less Than 60

°

F. 

 If the outdoor

temperature is less than 60

°

F, the unit is to be charged with the

room thermostat set in the “Heat” mode and the fan set in the
“Auto” position.

System Charging – Cooling Mode

The following describes adjusting the refrigerant charge with the
ambient temperature in excess of 60

°

F and the room thermostat

adjusted as indicated above.

At stabilized cooling conditions and with an outdoor temperature
of 

60

°

F

 or higher, the system should have from 9

°

F

 to 13

°

F

subcooling. For a proper subcooling reading, measure the
refrigerant pressure and temperature at the outdoor unit’s liquid
line service valve. If you have less than 9

°

F

 subcooling, add 

charge.

If you have more than 

13

°

F subcooling, remove charge.

While reaching the proper subcooling level, it is important to know
the discharge line temperature.  This temperature should be at
least 80

°

F over ambient or unit is flooding back to compressor.  If

flooding (i.e. low discharge line temperature) occurs, adjust valve
stem on expansion valve inward (clockwise viewing end of
expansion valve).  This will increase the super heat.

After achieving the proper subcooling and a sufficient discharge
temperature, make small adjustment to expansion valve stem to
reach 8

°

F to 10

°

F of super heat.  Adjusting the valve stem in

(clockwise), increases super heat.  Adjusting the valve stem out
(counter clockwise), decreases superheat .  If the system is
performing properly, reinstall the service port caps and the valve
bonnets.  With the valve opened, the valve bonnet is the primary
seal against refrigerant leaks. Apply two drops of clean oil to the
cap threads, allowing the oil to run down to the inner cap seal
surface.  Close caps finger-tight.  Then tighten cap additional two
to three hex flats.

System Charging – Heating Mode

The following method can be employed as a method to check the
system charge in the heating mode by measuring the hot gas
discharge at the compressor.

1.

Allow the system to operate for at least 20 minutes.

2.

Attach and insulate an electronic thermometer to the hot gas
discharge line mid way between the compressor and the re-
versing valve.  

Note: 

 The thermometer is to be well insulated

to prevent ambient influences.

3.

Adjust the charge to maintain a clear sight glass.

4.

Allow the compressor to operate for about 10 additional min-
utes and measure the hot gas discharge temperature.

5.

Using an additional electronic thermometer, measure the
ambient.

6.

Adjust the charge until the hot gas temperature equals 105

°

F + ambient (+ or – 5

°

F). Remove charge to increase the

temperature.

Note:

 

 When adjusting the charge, allow the compressor to

operate for about 10 minutes before taking readings.

Note: 

 Subsequent opening and replacement of the cap will

require only 1/2 to 1 hex flat. See the table below for the
torque required for an effective seal on the valve bonnet (1/6
turn past finger tight.

After closing the valve bonnet, perform a final refrigerant leak test
on the valves and sweat connections.  Return the room thermo-
stat to the desired settings.

XIV

DEFROST CONTROL (DC)

The CPLE uses a Time/Temperature method for defrost.  A thermal
sensor is attached to the condenser coil to determine the outdoor
coil temperature.  The coil temperature sensor is electrically
“Normally Open” and is wired to the electronic defrost control that
is located in the control box.

Both coil temperature and compressor run time determine de-
frosting of the outdoor coil. Adjustments to the defrost timing se-
lection can be changed from the 60 minute factory setting to ei-
ther 30 or 90 minutes by moving the jumper on the defrost con-
trol.  To initiate a defrost, the following statements must be true:

¾

The defrost sensor must be closed, and

¾

The compressor run time must equal the timing selection on
the defrost board.

Note:  

The compressor run time is accumulative during multiple

“heating” cycles.  The timer will reset to zero only when the de-
frost sensor returns to an open condition.  If the room thermostat
is operating in the “EM HT” mode, no accumulation of compres-
sor time is recorded.

Tubing Size

Torque (Foot-Pounds)

5/8

14

1-3/8

16

Table 8.

Summary of Contents for CPLE090

Page 1: ...1 INSTALLATION OPERATING INSTRUCTIONS 7 1 2 10 TON SPLIT SYSTEM HEAT PUMP 12 02 IO 229 GOODMAN MANUFACTURING COMPANY L P 2550 North Loop West Suite 400 Houston Texas 77092 www goodmanmfg com...

Page 2: ...0 10 Tons Series Identification CPLE Louvered Series Heat Pump WARNING III Product Description When matched with the appropriate airhandler s or evaporator coil s the CPLE090 120 heat pump complies wi...

Page 3: ...and obstruc tions such as walls or overhangs Note It is recommended that adequate service clearances also be considered Refrigerant System Requirements The selected site should be no greater than 50 b...

Page 4: ...refrigerant leaks Post Brazing Quench all welded joints with water or a wet rag Corner CPLE090 CPLE120 A 95 Lbs 110 Lbs B 95 Lbs 110 Lbs C 80 Lbs 85 Lbs D 95 Lbs 110 Lbs Arrange the straps to form a c...

Page 5: ...in accordance with the Canadian Electric Code CSA C22 1 Failure to observe this warning can result in electrical shock that can cause serious personal injury or death WARNING 220 216 4 100 x 4 216 400...

Page 6: ...the unit Refer to the latest edition of the National Electric Code or in Canada the Canadian Electric Code when determining the correct wire size The following table shows the current carrying capabi...

Page 7: ...found repair them After repair repeat the above pressure test If no leaks exist proceed to system evacuation WARNING WARNING Leak Testing To avoid possible explosion the line from the nitrogen cylinde...

Page 8: ...YLINDER C A B E D HIGH VACUUM PUMP LARGE DIAMETER BRAIDED VACUUM HOSES TO RELATED GAUGE PORTS OF COND UNIT HIGH VACUUM MANIFOLD LOW SIDE GAUGE HIGH SIDE GAUGE DIAL A CHARGE CHARGING CYLINDER THERMOCOU...

Page 9: ...oil to run down to the inner cap seal surface Close caps finger tight Then tighten cap additional two to three hex flats System Charging Heating Mode The following method can be employed as a method...

Page 10: ...driver blade until the reversing valve shifts This could take up to 21 seconds depending upon the position of the timing setting on the defrost board Immediately upon the action of the reversing valve...

Page 11: ...ect switch open 2 Blow fuse or fuse at disconnect switch 3 Thermostat set too high 4 Selector switch in Off position 5 Contactor and or relay coils burned out 6 Loose or open electrical connection in...

Page 12: ...ving to operate We use the highest quality materials and components available because if a part fails then the unit fails Finally every unit is run tested before it leaves the factory That s why we kn...

Reviews: