Goodman CPLE090 Installation & Operating Instructions Manual Download Page 6

6

Service Disconnect Box.   A service disconnect box is required as
per NEC.

Fuse – HACR Breakers
Protection is provided by either fuses or HACR type breakers.
Refer to the unit S&R plate and Table 7 for the maximum
overcurrent protection permitted.

Example

A CPLE120-3 is to be installed.  The distance from the
building breaker box to the unit is 75’.  Calculate the
minimum wire size assuming no more than 2% voltage drop.

MCA for CPLE120-3 = 43.3 (from S&R plate and table).

Applying previous table wire sizes less than #8 AWG cannot
be used for circuits which have a rating of 45A.  The #8
wire is not suitable since the maximum length for a 45A
circuit is 68’.  Solution, a #6 AWG wire is suitable up to
110’.  Note:  It is the contractors responsibility to follow the
NEC (USA) or CEC (Canada) when sizing the service wire
for this unit.

* Fuse or HACR Breaker of same value.

Line Voltage Wiring   ALL line voltage wiring is to be run through

conduit from the service disconnect box to the unit.  Refer to the

NEC (in Canada CEC) for the correct size conduit based on the
wire size.  The conduit is to enter the control box through the hole
provided in the bottom of the control box.  

Note:

 hole is sized for

¾” conduit.  If permitted by code, flexible conduit is preferred to
minimize vibration transmission from the unit to the building.

Connect the line voltage wires to the L1, L2, and L3 terminals of
the definite purpose contactor (located in the unit control box).
Refer to the wiring diagram attached to the unit when making
these connections.  

Note:

 the unit wiring diagram is also included

at the end of this manual.

¾

The wire size is appropriately sized to allow for no more than
a 2% voltage drop from the building breaker/fuse panel to the
unit.

¾

Refer to the latest edition of the National Electric Code, or in
Canada the Canadian Electric Code, when determining the
correct wire size.  The following table shows the current
carrying capabilities for copper conductors rated at 75

o

C with

a 2% voltage drop.

Model

*Max. Fuse

CPLE090-3

60

CPLE090-4

30

CPLE120-3

60

CPLE120-4

35

Wire Size

(AWG)

10

15

20

25

30

35

40

45

14

75

50

37

NR

NR

NR

NR

NR

12

118

79

59

47

NR

NR

NR

NR

10

188

125

95

75

63

54

NR

NR

8

301

201

150

120

100

86

75

68

6

471

314

235

188

157

134

118

110

Max. Allowable length in Feet to Limit Voltage drop to 2%

Min. Circuit Ampacity (MCA) – CPLE Unit

Based on NEC 1996

Table 6.

Table 7.

Figure 8.

Figure 9.

As noted elsewhere in this manual, this unit must be grounded.
The electrical ground circuit must consist of an appropriately sized
electrical wire connecting to the ground lug in the unit control box
and wire to the building electrical service panel.  Other methods
of grounding are permitted if performed in accordance with the
“National Electric Code” (NEC)/”American National Standards
Institute” (ANSI)/”National Fire Protection Association” (NFPA) 70
and local/state codes.  In Canada, electrical grounding is to be in
accordance with the Canadian Electric Code CSA C22.1.

Low Voltage Connections   The CPLE requires a 5-conductor low
voltage circuit from the room thermostat (without options). The
wires are to be no smaller than 18 AWG.  The field connection for
this circuit is to be made in the unit control box using solderless
connectors such as wire nuts.  See Figures 8 and 9 for a typical
low voltage hook-up.

SINGLE STAGE LOW VOLTAGE HOOK-UP

THERMOSTAT

O

W2

C

R

RED

BROWN

WHITE

BLUE

BLUE

WHITE

CONDENSING 

UNIT

CPLE090/120

AIR 

HANDLER
AH090/120

YELLOW

ORANGE

RED

Y

G

GREEN

TWO STAGES LOW VOLTAGE HOOK-UP

WHITE

BLUE

BLUE

WHITE

THERMOSTAT

YELLOW

ORANGE

RED

CONDENSING 

UNIT

CPLE090/120

Y

O

C

W1

R

RED

BROWN

GREEN

AIR 

HANDLER
AH090/120

G

W2

Summary of Contents for CPLE090

Page 1: ...1 INSTALLATION OPERATING INSTRUCTIONS 7 1 2 10 TON SPLIT SYSTEM HEAT PUMP 12 02 IO 229 GOODMAN MANUFACTURING COMPANY L P 2550 North Loop West Suite 400 Houston Texas 77092 www goodmanmfg com...

Page 2: ...0 10 Tons Series Identification CPLE Louvered Series Heat Pump WARNING III Product Description When matched with the appropriate airhandler s or evaporator coil s the CPLE090 120 heat pump complies wi...

Page 3: ...and obstruc tions such as walls or overhangs Note It is recommended that adequate service clearances also be considered Refrigerant System Requirements The selected site should be no greater than 50 b...

Page 4: ...refrigerant leaks Post Brazing Quench all welded joints with water or a wet rag Corner CPLE090 CPLE120 A 95 Lbs 110 Lbs B 95 Lbs 110 Lbs C 80 Lbs 85 Lbs D 95 Lbs 110 Lbs Arrange the straps to form a c...

Page 5: ...in accordance with the Canadian Electric Code CSA C22 1 Failure to observe this warning can result in electrical shock that can cause serious personal injury or death WARNING 220 216 4 100 x 4 216 400...

Page 6: ...the unit Refer to the latest edition of the National Electric Code or in Canada the Canadian Electric Code when determining the correct wire size The following table shows the current carrying capabi...

Page 7: ...found repair them After repair repeat the above pressure test If no leaks exist proceed to system evacuation WARNING WARNING Leak Testing To avoid possible explosion the line from the nitrogen cylinde...

Page 8: ...YLINDER C A B E D HIGH VACUUM PUMP LARGE DIAMETER BRAIDED VACUUM HOSES TO RELATED GAUGE PORTS OF COND UNIT HIGH VACUUM MANIFOLD LOW SIDE GAUGE HIGH SIDE GAUGE DIAL A CHARGE CHARGING CYLINDER THERMOCOU...

Page 9: ...oil to run down to the inner cap seal surface Close caps finger tight Then tighten cap additional two to three hex flats System Charging Heating Mode The following method can be employed as a method...

Page 10: ...driver blade until the reversing valve shifts This could take up to 21 seconds depending upon the position of the timing setting on the defrost board Immediately upon the action of the reversing valve...

Page 11: ...ect switch open 2 Blow fuse or fuse at disconnect switch 3 Thermostat set too high 4 Selector switch in Off position 5 Contactor and or relay coils burned out 6 Loose or open electrical connection in...

Page 12: ...ving to operate We use the highest quality materials and components available because if a part fails then the unit fails Finally every unit is run tested before it leaves the factory That s why we kn...

Reviews: