Goodman CPLE090 Installation & Operating Instructions Manual Download Page 10

10

During defrost the following actions occur:

1.

The reversing valve is energized and the heat pump
operates in the cooling mode.

2.

The airhandler auxiliary heat (if equipped) is activated.

3.

The condenser fan motor is shut-off.

If the defrost cycle has not terminated after ten (10) minutes the
control will override the defrost sensor and revert to a heating
mode.

The defrost control has test pins which can be useful when trouble-
shooting in the heating mode. These test pins accelerate the com-
pressor run time counter.  The suggested method for accessing
this feature is:

A. Run unit in heat mode.

B. Check unit for proper charge.

Note:

 Bands of frost indicate low refrigerant charge.

C. Shut off power to unit.

D. Disconnect outdoor fan by removing the purple lead from

the Condenser Fan Defrost Relay.

E. Restart unit and allow frost to accumulate.

F. After a few minutes the defrost thermostat should close.

To verify the position of the thermostat check for 24V
between “DFT” and “C” on the defrost board.  Should the
defrost thermostat fail to close after a heavy build-up of
frost and the thermostat is less than 28

°

, the thermostat is

to be replaced.

G. After the thermostat has closed, short across the test pins

with the a screwdriver blade until the reversing valve
shifts.  This could take up to 21 seconds depending upon
the position of the timing setting on the defrost board.
Immediately upon the action of the reversing valve,
remove the short.  

Note:

  If this short is not removed

immediately, the defrost activity will last only 2.3 seconds.

H. After defrost has terminated (up to 10 minutes) check the

defrost thermostat for 24V between “DFT” and “C”.  This
reading should be 0 V (open sensor).

I. Shut off power to the unit.

J. Replace outdoor fan motor wire removed in Step D.

XV    TROUBLE SHOOTING

QUALIFIED INSTALLER/SERVICER ONLY

When troubleshooting, the first step should always be to check
for clean coils, clean filter(s), and proper airflow. Indoor airflow
should be 375 to 425 CFM per ton of cooling based on the size of
the outdoor unit. The most common way of establishing indoor
airflow is heating temperature rise. Indoor airflow will then be
(Heating output of equipment) / (1.1 x temp. rise). In other cases,
measurement of external static pressure is helpful. For details,
see the Installation Operator Instructions for your indoor
equipment.

3 Phase Scroll Compressor

The CPLE090/120 condenser is equipped with a 3-phase
scroll compressor.  If the unit sounds noisy and/or the suction
and liquid pressures are almost equal, the compressor is
operating in the reverse rotation.  Reverse (2) incoming
power supply leads.

CAUTION

SHUNT

SELECTION

JUMPER

Figure 12.

Summary of Contents for CPLE090

Page 1: ...1 INSTALLATION OPERATING INSTRUCTIONS 7 1 2 10 TON SPLIT SYSTEM HEAT PUMP 12 02 IO 229 GOODMAN MANUFACTURING COMPANY L P 2550 North Loop West Suite 400 Houston Texas 77092 www goodmanmfg com...

Page 2: ...0 10 Tons Series Identification CPLE Louvered Series Heat Pump WARNING III Product Description When matched with the appropriate airhandler s or evaporator coil s the CPLE090 120 heat pump complies wi...

Page 3: ...and obstruc tions such as walls or overhangs Note It is recommended that adequate service clearances also be considered Refrigerant System Requirements The selected site should be no greater than 50 b...

Page 4: ...refrigerant leaks Post Brazing Quench all welded joints with water or a wet rag Corner CPLE090 CPLE120 A 95 Lbs 110 Lbs B 95 Lbs 110 Lbs C 80 Lbs 85 Lbs D 95 Lbs 110 Lbs Arrange the straps to form a c...

Page 5: ...in accordance with the Canadian Electric Code CSA C22 1 Failure to observe this warning can result in electrical shock that can cause serious personal injury or death WARNING 220 216 4 100 x 4 216 400...

Page 6: ...the unit Refer to the latest edition of the National Electric Code or in Canada the Canadian Electric Code when determining the correct wire size The following table shows the current carrying capabi...

Page 7: ...found repair them After repair repeat the above pressure test If no leaks exist proceed to system evacuation WARNING WARNING Leak Testing To avoid possible explosion the line from the nitrogen cylinde...

Page 8: ...YLINDER C A B E D HIGH VACUUM PUMP LARGE DIAMETER BRAIDED VACUUM HOSES TO RELATED GAUGE PORTS OF COND UNIT HIGH VACUUM MANIFOLD LOW SIDE GAUGE HIGH SIDE GAUGE DIAL A CHARGE CHARGING CYLINDER THERMOCOU...

Page 9: ...oil to run down to the inner cap seal surface Close caps finger tight Then tighten cap additional two to three hex flats System Charging Heating Mode The following method can be employed as a method...

Page 10: ...driver blade until the reversing valve shifts This could take up to 21 seconds depending upon the position of the timing setting on the defrost board Immediately upon the action of the reversing valve...

Page 11: ...ect switch open 2 Blow fuse or fuse at disconnect switch 3 Thermostat set too high 4 Selector switch in Off position 5 Contactor and or relay coils burned out 6 Loose or open electrical connection in...

Page 12: ...ving to operate We use the highest quality materials and components available because if a part fails then the unit fails Finally every unit is run tested before it leaves the factory That s why we kn...

Reviews: