Goodman CPLE090 Installation & Operating Instructions Manual Download Page 4

4

 

 

 

Suction Line Insulation.  All suction lines are to be insulated with
a recognized tubing insulation that is a minimum of 3/8" thick.

Solder. Solder should consist of a minimum of 2% silver.

Hangers and Isolation.  All refrigerant lines are to be isolated from
the structure and supported with hangers.  See Figure 4 below for
details.

Inverted Suction Line Loop.  When the condenser is located at
the same level or above the evaporator section, an inverted loop
is to be employed on the suction line.  This practice will prevent
liquid refrigerant from migrating into the compressor during
shutdown.  See 

Figure 5.

X

Refrigerant Tubing

To avoid overheating of the service valves, protect the valve
with a wet rag or similar approved thermal heat trap. Failure to
observe this practice can result in damage to the valve.

As previously noted, protective clothing and eye protection
should be used when making any welded connection.

Preparing the Tubing.  All cut ends are to be round, burr free
and cleaned.  Failure to follow this practice increases the
chances for refrigerant leaks.

Post Brazing.  Quench all welded joints with water or a wet rag.

Corner

CPLE090

CPLE120

A

95 Lbs.

110 Lbs.

B

95 Lbs.

110 Lbs.

C

80 Lbs.

85 Lbs.

D

95 Lbs.

110 Lbs.

Arrange the straps to form a central suspension point (see Figure
2 for details).  When raising and setting the unit, observe all
safety rules.  When the unit is in position, the wooden shipping
skid, all protection and lifting materials are to be removed.

IX

Unit Corner Weight

The following table and sketch are to be used for determining
the unit corner weight.  The unit net weight and shipping weight
is provided in the “Product Description” section, Page 2, of this
manual.

A

35.500"

35.500"

C

D

B

41.500"

Oil Return.  To facilitate oil return to the compressor, a horizon-
tal suction line should be pitched (1/2" per 10’) toward the
condensing unit.

L = Liquid Line     S = Suction Line       * = Full Rating  Line Size

Figure 3.

Table 3.

Piping Size  Use a carefully estimated length of refrigerant tubing
(distance between condenser and evaporator). Apply the
following table to determine the tubing diameter:

WARNING

Table 2.

Figure 4.

Figure 5.

MODEL

L

S

L

S

L

S

L

S

CPLE090

5/8

1-1/8

5/8

1-3/8

5/8

1-3/8

5/8

1-3/8

CPLE120

5/8

1-3/8

5/8

1-5/8

5/8

1-5/8

5/8

1-5/8

50' - 74'

75' - 99'

Outside Diameter Line Size (in.)

0' - 24'

*25' - 49'

Summary of Contents for CPLE090

Page 1: ...1 INSTALLATION OPERATING INSTRUCTIONS 7 1 2 10 TON SPLIT SYSTEM HEAT PUMP 12 02 IO 229 GOODMAN MANUFACTURING COMPANY L P 2550 North Loop West Suite 400 Houston Texas 77092 www goodmanmfg com...

Page 2: ...0 10 Tons Series Identification CPLE Louvered Series Heat Pump WARNING III Product Description When matched with the appropriate airhandler s or evaporator coil s the CPLE090 120 heat pump complies wi...

Page 3: ...and obstruc tions such as walls or overhangs Note It is recommended that adequate service clearances also be considered Refrigerant System Requirements The selected site should be no greater than 50 b...

Page 4: ...refrigerant leaks Post Brazing Quench all welded joints with water or a wet rag Corner CPLE090 CPLE120 A 95 Lbs 110 Lbs B 95 Lbs 110 Lbs C 80 Lbs 85 Lbs D 95 Lbs 110 Lbs Arrange the straps to form a c...

Page 5: ...in accordance with the Canadian Electric Code CSA C22 1 Failure to observe this warning can result in electrical shock that can cause serious personal injury or death WARNING 220 216 4 100 x 4 216 400...

Page 6: ...the unit Refer to the latest edition of the National Electric Code or in Canada the Canadian Electric Code when determining the correct wire size The following table shows the current carrying capabi...

Page 7: ...found repair them After repair repeat the above pressure test If no leaks exist proceed to system evacuation WARNING WARNING Leak Testing To avoid possible explosion the line from the nitrogen cylinde...

Page 8: ...YLINDER C A B E D HIGH VACUUM PUMP LARGE DIAMETER BRAIDED VACUUM HOSES TO RELATED GAUGE PORTS OF COND UNIT HIGH VACUUM MANIFOLD LOW SIDE GAUGE HIGH SIDE GAUGE DIAL A CHARGE CHARGING CYLINDER THERMOCOU...

Page 9: ...oil to run down to the inner cap seal surface Close caps finger tight Then tighten cap additional two to three hex flats System Charging Heating Mode The following method can be employed as a method...

Page 10: ...driver blade until the reversing valve shifts This could take up to 21 seconds depending upon the position of the timing setting on the defrost board Immediately upon the action of the reversing valve...

Page 11: ...ect switch open 2 Blow fuse or fuse at disconnect switch 3 Thermostat set too high 4 Selector switch in Off position 5 Contactor and or relay coils burned out 6 Loose or open electrical connection in...

Page 12: ...ving to operate We use the highest quality materials and components available because if a part fails then the unit fails Finally every unit is run tested before it leaves the factory That s why we kn...

Reviews: