Goodman CPLE090 Installation & Operating Instructions Manual Download Page 3

3

VII

Typical Installations

The typical locations for the CPLE unit are slab mounted and roof
mounted.  For unit weight data, see the "Product Description" sec-
tion of this manual.

Slab Mounting.  The slab 

MUST

 be capable of supporting the weight

of the unit.  The slab should be a minimum of 6" wider than the unit
in all directions.  If required, the slab should be elevated to protect
the unit from water damage due to flooding.  Before installing the
unit onto a slab, the wooden shipping skid 

MUST

 be removed.

Roof Mounting.  Give careful consideration to the load carrying
capability of the roof.  If possible, locate the unit where walls or
partitions can offer additional support.  If doubt exists regarding
the integrity of the roof or its supporting structure, consult a struc-
tural engineer.

VIII

Rigging

All panels 

MUST

 be in position and secured before lifting this

equipment.

Figure 1.

12"

12"

12"

60"

24"

WARNING

VI

Site Selection

This unit is designed for outdoor installations only.

Air Supply.  The CPLE products are air-cooled heat pumps.  To
ensure the optimum unit performance, the installation site should
provide unobstructed airflow.  See Figure 1 for minimum clear-
ances from other air-cooled condensers/heat pumps and obstruc-
tions such as walls or overhangs. 

Note: 

 It is recommended that

adequate service clearances also be considered.

Refrigerant System Requirements.   The selected site should be
no greater than 50’ below or 70’ above the evaporator section.
For optimum performance, the minimum length interconnecting
tubing is preferred.  When possible minimize the amount of bends
and turns.

Wiring and Tubing Protection.  Electrical wiring and refrigerant
tubing is to be protected from damage due to incidental contact
such as being walked upon.

Vibration and Sound Control.  The CPLE series is engineered to
produce the minimum sound and vibration.  To minimize the
possibility of either sound or vibration issues, the CPLE 

condenser

is to be securely mounted to a surface that is:

¾

Solid

¾

Greatest practical mass

¾

Ridged

¾

Minimum radiating surface

When possible the slab for a ground level unit should not be
connected to the wall or the building.

Prohibited Locations.  Do not locate this unit in the following
locations:

¾

Inside a building

¾

Directly under a vent termination from a gas appliance

¾

Within 3 feet of a clothes dryer vent

¾

Where water may rise into the unit

Figure 2.

When lifting the unit, use spreader bars (field supplied).  This prac-
tice will minimize the possibility of lifting cable/straps damage. Also,
to protect the cabinet louvers, the use of protective material such
as plywood behind the cables/straps is recommended.

Summary of Contents for CPLE090

Page 1: ...1 INSTALLATION OPERATING INSTRUCTIONS 7 1 2 10 TON SPLIT SYSTEM HEAT PUMP 12 02 IO 229 GOODMAN MANUFACTURING COMPANY L P 2550 North Loop West Suite 400 Houston Texas 77092 www goodmanmfg com...

Page 2: ...0 10 Tons Series Identification CPLE Louvered Series Heat Pump WARNING III Product Description When matched with the appropriate airhandler s or evaporator coil s the CPLE090 120 heat pump complies wi...

Page 3: ...and obstruc tions such as walls or overhangs Note It is recommended that adequate service clearances also be considered Refrigerant System Requirements The selected site should be no greater than 50 b...

Page 4: ...refrigerant leaks Post Brazing Quench all welded joints with water or a wet rag Corner CPLE090 CPLE120 A 95 Lbs 110 Lbs B 95 Lbs 110 Lbs C 80 Lbs 85 Lbs D 95 Lbs 110 Lbs Arrange the straps to form a c...

Page 5: ...in accordance with the Canadian Electric Code CSA C22 1 Failure to observe this warning can result in electrical shock that can cause serious personal injury or death WARNING 220 216 4 100 x 4 216 400...

Page 6: ...the unit Refer to the latest edition of the National Electric Code or in Canada the Canadian Electric Code when determining the correct wire size The following table shows the current carrying capabi...

Page 7: ...found repair them After repair repeat the above pressure test If no leaks exist proceed to system evacuation WARNING WARNING Leak Testing To avoid possible explosion the line from the nitrogen cylinde...

Page 8: ...YLINDER C A B E D HIGH VACUUM PUMP LARGE DIAMETER BRAIDED VACUUM HOSES TO RELATED GAUGE PORTS OF COND UNIT HIGH VACUUM MANIFOLD LOW SIDE GAUGE HIGH SIDE GAUGE DIAL A CHARGE CHARGING CYLINDER THERMOCOU...

Page 9: ...oil to run down to the inner cap seal surface Close caps finger tight Then tighten cap additional two to three hex flats System Charging Heating Mode The following method can be employed as a method...

Page 10: ...driver blade until the reversing valve shifts This could take up to 21 seconds depending upon the position of the timing setting on the defrost board Immediately upon the action of the reversing valve...

Page 11: ...ect switch open 2 Blow fuse or fuse at disconnect switch 3 Thermostat set too high 4 Selector switch in Off position 5 Contactor and or relay coils burned out 6 Loose or open electrical connection in...

Page 12: ...ving to operate We use the highest quality materials and components available because if a part fails then the unit fails Finally every unit is run tested before it leaves the factory That s why we kn...

Reviews: