Goodman CPLE090 Installation & Operating Instructions Manual Download Page 11

11

TROUBLE SHOOTING ANALYSIS TABLE 

 

COMPLAINT 

PROBABLE CAUSE 

REMEDY 

1. High Head Pressure 

1. Excessive charge of refrigerant in system. 
2. Inadequate supply of air across the 

condenser coil. 

3. Non-condensate gases in the system. 

1. Purge or pump-down excessive charge. 
2. Make certain that coil is not fouled in any 

way, or that air is not re-circulating. 

3. Purge these gases from the system. 

Recharge system, if necessary. 

2. Low Head Pressure 

1. System low on refrigerant. 
2. Compressor valves broken. 

1. Charge system until sight glass is clear of bubbles. 
2. Replace compressor. 

3. Low Suction Pressure 

1. Liquid line valve closed. 
2. Restricted liquid line. 
3. The bulb of the thermal expansion valve 

has lost its charge. 

 
4. System low on refrigerant. 
 
5. Dirty filters. 
6. Coil frosted up. 
7. Flash gas in the liquid line. 
8. Quantity of air through evaporator not 
adequate. 

1. Open the liquid line valve. 
2. Replace filter-dryer. 
3. Detach the bulb from the suction line and hold 

in one hand. If no liquid refrigerant goes through 
the valve, replace the valve. 

4. Test the unit for leaks. Add refrigerant until sight 

glass is free from bubbles, after repairing leak. 

5. Clean or replace filter. 
6. Defrost and clean coil. Clean or replace filters. 
7. Excessive liquid line drop. Check liquid line size. 
8. Increase the blower speed. 

4. High Suction Pressure 

1. Expansion valve stuck open. 
2. Expansion valve bulb not in contact with 

suction line. 

3. Suction and/or discharge valve leaking or 
broken. 

1. Correct valve action or replace the valve. 
2. Fasten bulb securely to suction line. 
 
3. Replace compressor. 

5. Compressor will not 
start. 

1. Disconnect switch open. 
2. Blow fuse or fuse at disconnect switch. 
3. Thermostat set too high. 
4. Selector switch in "Off" position. 
5. Contactor and/or relay coils burned out. 
6. Loose or open electrical connection in either 

the control or power circuit. 

1. Close the disconnect switch. 
2. Check the cause of failure and replace the fuse. 
3. Adjust to lower temperature. 
4. Turn selector switch knob to "Cool" position. 
5. Replace contactor and/or relay. 
6. Inspect and secure all electrical connections. 

The following information is intended for qualified service companies only.

Common causes for unsatisfactory operation of heat pumps in the heating mode include:

Dirty Filters

Dirty filters or inadequate airflow through the indoor coil.  Failure
to keep clean filters and adequate airflow (375-425 CFM/ton) will
cause excessive discharge pressures that may cause the high-
pressure switch to function.

Low Return Air Temperatures

Return ductwork temperatures that are less than 60°F will cause
low discharge pressure, low suction pressure and excessive
defrost cycling.

Undercharging

An undercharged system will cause low discharge pressure, low
suction pressure and an accumulation of frost on the lower section
of the outdoor coil.

Poor Termination of Defrost

The defrost sensor must make good contact with the outside coil
return bend or a non-termination of defrost may occur.

Reversing Valve

A reversing valve may not function correctly for the following
reasons:

1.

Solenoid does not energize when voltage is present

Replace the reversing valve.

2.

No voltage to the solenoid

Check the wiring.

3.

The valve will not shift
a. Undercharged

Check for leaks

b. Valve body damage

Replace the reversing valve

c. Valve sticking

Replace the reversing valve

TROUBLESHOOTING ANALYSIS TABLE - COOLING

TROUBLESHOOTING ANALYSIS - HEATING

Summary of Contents for CPLE090

Page 1: ...1 INSTALLATION OPERATING INSTRUCTIONS 7 1 2 10 TON SPLIT SYSTEM HEAT PUMP 12 02 IO 229 GOODMAN MANUFACTURING COMPANY L P 2550 North Loop West Suite 400 Houston Texas 77092 www goodmanmfg com...

Page 2: ...0 10 Tons Series Identification CPLE Louvered Series Heat Pump WARNING III Product Description When matched with the appropriate airhandler s or evaporator coil s the CPLE090 120 heat pump complies wi...

Page 3: ...and obstruc tions such as walls or overhangs Note It is recommended that adequate service clearances also be considered Refrigerant System Requirements The selected site should be no greater than 50 b...

Page 4: ...refrigerant leaks Post Brazing Quench all welded joints with water or a wet rag Corner CPLE090 CPLE120 A 95 Lbs 110 Lbs B 95 Lbs 110 Lbs C 80 Lbs 85 Lbs D 95 Lbs 110 Lbs Arrange the straps to form a c...

Page 5: ...in accordance with the Canadian Electric Code CSA C22 1 Failure to observe this warning can result in electrical shock that can cause serious personal injury or death WARNING 220 216 4 100 x 4 216 400...

Page 6: ...the unit Refer to the latest edition of the National Electric Code or in Canada the Canadian Electric Code when determining the correct wire size The following table shows the current carrying capabi...

Page 7: ...found repair them After repair repeat the above pressure test If no leaks exist proceed to system evacuation WARNING WARNING Leak Testing To avoid possible explosion the line from the nitrogen cylinde...

Page 8: ...YLINDER C A B E D HIGH VACUUM PUMP LARGE DIAMETER BRAIDED VACUUM HOSES TO RELATED GAUGE PORTS OF COND UNIT HIGH VACUUM MANIFOLD LOW SIDE GAUGE HIGH SIDE GAUGE DIAL A CHARGE CHARGING CYLINDER THERMOCOU...

Page 9: ...oil to run down to the inner cap seal surface Close caps finger tight Then tighten cap additional two to three hex flats System Charging Heating Mode The following method can be employed as a method...

Page 10: ...driver blade until the reversing valve shifts This could take up to 21 seconds depending upon the position of the timing setting on the defrost board Immediately upon the action of the reversing valve...

Page 11: ...ect switch open 2 Blow fuse or fuse at disconnect switch 3 Thermostat set too high 4 Selector switch in Off position 5 Contactor and or relay coils burned out 6 Loose or open electrical connection in...

Page 12: ...ving to operate We use the highest quality materials and components available because if a part fails then the unit fails Finally every unit is run tested before it leaves the factory That s why we kn...

Reviews: