SERVICING
18
CHECKING TEMPERATURE RISE
The more air (CFM) being delivered through a given furnace,
the less the rise will be; so the less air (CFM) being delivered,
the greater the rise. The temperature rise should be adjusted
in accordance to a given furnace specifications and its
external static pressure. An incorrect temperature rise may
result in condensing in or overheating of the heat exchanger.
An airflow and temperature rise table is provided in the blower
performance specification section. Determine and adjust
temperature rise as follows:
1. Operate furnace with burners firing for approximately ten
minutes. Check BTU input to furnace - do not exceed
input rating stamped on rating plate. Ensure all registers
are open and all duct dampers are in their final (fully or
partially open) position.
2. Place thermometers in the return and supply ducts as
close to the furnace as possible. Thermometers must not
be influenced by radiant heat by being able to “see” the
heat exchanger.
SUPPLY
AIR
RETURN
AIR
Checking Temperature Rise
3. Subtract the return air temperature from the supply air
temperature to determine the air temperature rise. Allow
adequate time for thermometer readings to stabilize.
4. Adjust temperature rise by adjusting the circulator blower
speed. Increase blower speed to reduce temperature rise.
Decrease blower speed to increase temperature rise.
Refer to
Circulator Blower Speed
section in the Product
Design section of this manual for speed changing details.
Temperature rise is related to the BTUH output of the
furnace and the amount of air (CFM) circulated over the
heat exchanger. Measure motor current draw to determine
that the motor is not overloaded during adjustments.
CHECKING PRIMARY LIMIT CONTROL
All use a nonadjustable, automatic reset, bi-metal type limit
control.
Style 1 drawing illustrates the Primary Limit used on the 80%
furnaces.
Style 1
WARNING
HIGH
VOLTAGE
D
I
S
CONNECT
ALL
POWE
R
BEFO
R
E
S
E
R
VICING
O
R
CHANGING
ANY
ELECT
R
ICAL
WI
R
ING.
M
ULTIPLE
POWE
R
S
OU
R
CE
S
MAY
BE
P
R
E
S
ENT.
F
AILU
R
E
TO
DO
S
O
MAY
CAU
S
E
P
R
OPE
R
TY
DAMAGE,
PE
RS
ONAL
IN
J
U
R
Y
O
R
DEATH.
1. Remove burner compartment door to gain access to
the primary limit.
2. Remove low voltage wires at limit control terminals.
3. With an ohmmeter, test between these two terminals
as shown in the following drawing. The ohmmeter
should read continuous unless heat exchanger tem-
perature is above limit control setting. If not as above,
replace the control.
COLOR
IDENTIFYING
TAB
Testing Primary Limit Control
Summary of Contents for Amana AMES80 U Series
Page 24: ...TROUBLESHOOTING 24...
Page 25: ...TROUBLESHOOTING 25...