SYSTEM OPERATION
7
CAUTION
T
O
P
R
EVENT
UN
R
ELIABLE
OPE
R
ATION
O
R
E
Q
UIPMENT
DAMAGE,
THE
INLET
GA
S S
UPPLY
P
R
E
SS
U
R
E
MU
S
T
BE
A
S S
PECIFIED
ON
THE
UNIT
R
ATING
PLATE
WITH
ALL
OTHE
R
HOU
S
EHOLD
GA
S
FI
R
ED
APPLIANCE
S
OPE
R
ATING.
Inlet gas supply pressures must be maintained within the
ranges specified below. The supply pressure must be constant
and available with all other household gas fired appliances
operating. The minimum gas supply pressure must be
maintained to prevent unreliable ignition. The maximum must
not be exceeded to prevent unit overfiring.
Natural Gas
Minimum: 4.5" w.c.
Maximum: 10.0" w.c.
Propane Gas Minimum: 11.0" w.c. Maximum: 13.0" w.c.
INLET GAS SUPPLY PRESSURE
GAS VALVE
This unit is equipped with a 24 volt gas valve controlled during
furnace operation by the integrated control module. Taps for
measuring the gas supply pressure and manifold pressure
are provided on the valve.
NOTE: The gas supply pressure on White-Rodger “J”
model gas valve, used on single stage furnaces, can be
checked with a gas pressure test kit (Part #0151K00000S)
available through our authorized distributors.
The gas valve has a manual ON/OFF control located on the
valve itself. This control may be set only to the “ON” or “OFF”
position. Refer to the
Lighting Instructions Label
section of this
manual or the installation instructions for use of this control
during start up and shut down periods.
GAS PIPING CONNECTIONS
CAUTION
To avoid possible unsatisfactory operation or
equipment damage due to underfiring of equipment,
use the proper size of natural gas piping needed when
running pipe from the meter to the furnace.
The gas piping supplying the furnace must be properly
sized based on the gas flow required, specific gravity of the
gas, and length of the run. The gas line installation must
comply with local codes, or in their absence, with the latest
edition of the National Fuel Gas Code, NFPA 54/ANSI
Z223.1.
Length of
Nominal Black Pipe Size
Pipe in Feet
1/2"
3/4"
1"
1 1/4"
1 1/2"
10
132
278
520
1050
1600
20
92
190
350
730
1100
30
73
152
285
590
980
40
63
130
245
500
760
50
56
115
215
440
670
60
50
105
195
400
610
70
46
96
180
370
560
80
43
90
170
350
530
90
40
84
160
320
490
100
38
79
150
305
460
CFH =
(Pressure 0.5 psig or less and pressure drop of 0.3" W.C.; Based on 0.60 Specific
Gravity Gas)
Natural Gas Capacity of Pipe
In Cubic Feet of Gas Per Hour (CFH)
BTUH Furnace Input
Heating Value of Gas (BTU/Cubic Foot)
GAS PIPING CHECKS
Before placing unit in operation or upon completion of
servicing, leak test the unit and gas connections.
WARNING
T
O
AVOID
THE
PO
SS
IBLITY
OF
E
X
PLO
S
ION
O
R
FI
R
E,
NEVE
R
U
S
E
A
MATCH
O
R
OPEN
FLAME
TO
TE
S
T
FO
R
LEA
KS
.
Check for leaks using an approved chloride-free soap and
water solution, an electronic combustible gas detector, or
other approved testing methods.
NOTE:
Never exceed specified pressures for testing. Higher
pressure may damage the gas valve and cause subsequent
overfiring, resulting in heat exchanger failure. Disconnect
this unit and shutoff valve from the gas supply piping system
before pressure testing the supply piping system with
pressures in excess of 1/2 psig (3.48 kPa). Isolate this unit
from the gas supply piping system by closing its external
manual gas shutoff valve before pressure testing supply
piping system with test pressures equal to or less than 1/2
psig (3.48 kPa).
CAUTION
E
DGE
S
OF
S
HEET
METAL
HOLE
S
MAY
BE
S
HA
R
P.
U
S
E
GLOVE
S
A
P
R
ECAUTION
WHEN
R
EMOVING
HOLE
PLUG
S
.
Summary of Contents for Amana AMES80 U Series
Page 24: ...TROUBLESHOOTING 24...
Page 25: ...TROUBLESHOOTING 25...