background image

9

IO-230F

08/04

To complete the conversion, slide the evaporator coil into

the chassi

s and attach the three (3) access panel

s. 

(Figure

7).

CONVERSION TO HORIZONTAL

The “B” series product is not suitable for horizontal
application and must not be used for this type of installation.
The following describes converting to “Horizontal Left-
Hand”.  The only field modification required for conversion
to “Horizontal Right-Hand” is the removal of the plastic
knockouts in the horizontal panel drain connections.

 

TOP OF WRAPPER

INSULATION JACKET

ZEE COIL SUPPORT

WRAPPER STIFFENER

DRAIN PAN INSULATION
DPI KIT (HATCHED AREA)

NEOPRENE GASKET

MOTOR

BLOWER

Figure 7

As shown in 

Figure 8

, it is recommended that the

conversion to horizontal be performed before placing the
air handler in its final location and in an area that allows for
access to all sides.

1.

Remove the (3) air handler access panels.

2.

Remove the “J” shaped bracket that retains the
evaporator coil.

3.

Remove the flowrater (or TXV) from the lower left side
access panel and slide out the evaporator coil and
horizontal drain pan.

4.

Remove the gasket from the horizontal pan drain
connections.

5.

Remove the oval shaped plastic plug from the left side
access panel.  Remove the oval shaped rubber gasket
seal from the lower right side access panel.

6.

The drain connections for the horizontal pan are sealed
with a thin coating of plastic.  Carefully knock out this
plastic seal with a screwdriver and hammer.  

Note:

The upper drain will become the secondary drain
which is mandatory in many municipalities .

7.

Install the plastic plug removed in step 5 to the right
side lower access panel and the oval shaped rubber
gasket to the lower left access panel.

8.

Reinstall the evaporator coil with the horizontal panel
on the left side.  Note: Push the assembly completely
to the rear to ensure the engagement of the upflow
pan with the rear channel bracket.

9.

Install the “J” bracket (removed in step 2) to support
the upflow pan to the tie channel.

10. Attach all panels and the refrigerant management

device.

 

 

Secondary Drain 

Primary Drain 

Figure 8

CONDENSATE REMOVAL

The drain pan has a primary and secondary drain
connection (Figure 8).  Condensate removal is performed
by attaching a ¾” PVC pipe to the evaporator coil pan and
terminated in accordance with local or state Plumbing/
HVAC codes. The installation must include a “P” style trap
that is located as close as is practical to the evaporator
coil.  Exercise caution not to over-tighten the drain
connection(s) in order to prevent possible damage to the
evaporator drain pan.  See 

Figure 9 

for details of a typical

condensate line “P” trap.

Installations that are above a finished ceiling may require
a field supplied auxiliary drain pan.  Consult local codes on
this requirement.

DRAIN

CONNECTION

2" MINIMUM

3" MINIMUM

POSITIVE LIQUID

SEAL (REQ'D) 

UNIT

FLEXIBLE

TUBING (HOSE

OR PIPE)

Figure 9

Use of a condensate removal pump is permitted when
necessary. This condensate pump should have provisions
for shutting off the control voltage should a blocked drain
occur. A trap must be installed between the unit and the
condensate pump.

Summary of Contents for AEPT

Page 1: ...Company L P IO 230F 2550 North Loop West Suite 400 Houston Texas 77092 08 04 www goodmanmfg com or www amana hac com 2003 2004 Goodman Manufacturing Company L P INSTALLATION OPERATING INSTRUCTIONS FO...

Page 2: ...092 713 861 2500 IMPORTANT SAFETY INSTRUCTIONS Recognize Safety Symbols Words and Labels The following symbols and labels are used throughout this manual to indicate immediate or potential hazards It...

Page 3: ...area such as a garage utility room or parking area and a carbon monoxide producing device is operated therein there must be adequate direct outside ventilation This ventilation is necessary to avoid t...

Page 4: ...USTAGREE UNLESS USING HKR3 3 PHASE SERIES HEAT KIT THIS AIR HANDLER DOES NOT HAVE FACTORY INSTALLED ELECTRIC HEAT ELECTRIC HEAT ISAVAILABLE AS AN ACCESSORY IF INSTALLING THIS OPTION THE ONLY HEAT KITS...

Page 5: ...OR OBJECTIONABLE FUMES ODORS INTO THE DUCTWORK The return ductwork is to be introduced into the air handler bottom upflow configuration Return Air Filters Each installation must include a return air f...

Page 6: ...e building supply connects to the stripped black and white wires contained in the air handler electrical compartment cavity Aground screw is also contained in this area Attach the supply wires to the...

Page 7: ...NT NOTE In order to prevent damage to the sensing bulb it is not permanently installed in the factory This bulb is to be removed prior to brazing Place in proper location after braze joint has cooled...

Page 8: ...that allows for access to all sides To prevent the evaporator coil pan from sweating the DPI accessory insulation kit is to be used when performing this conversion Note The DPI kit is not supplied wi...

Page 9: ...te The upper drain will become the secondary drain which is mandatory in many municipalities 7 Install the plastic plug removed in step 5 to the right side lower access panel and the oval shaped rubbe...

Page 10: ...n the OFF position For most applications this setting is to be changed according to the electric heat size and the outdoor unit selection The AEPT product uses a General Electric ECMTM motor This moto...

Page 11: ...PT MODELS SEE SUPPLEMENTAL INSTALLATION AND OPERATING INSTRUCTIONS FOR AEPT MODELS ROOM THERMOSTAT W Y G R 18 GA 4 WIRES WITH COOLING 3 WIRES WITHOUT R G W Y TO CONDENSING UNIT 24V CONNECTIONS 18 GA 2...

Page 12: ...UF ARPF ARPT 18 60 ABOVE 10 KW HEAT PUMP B L U E W H I T E C W2 R E D Y O R R Y C O W2 18 GA 7 WIRE R G E R AR UNIT RED OT 1 OT 2 3 EHR 1 2 4 BROWN SEE NOTE 2 NOTES 1 OUTDOOR THERMOSTAT OT 1 SHOULD BE...

Page 13: ...y available Follow the thermostat manufacturer s instruction for installation START UP PROCEDURE Prior to start up ensure that all electrical connections are properly sized and tightened All panels mu...

Reviews: