When matched with a Goodman or Amana brand
condenser or heat pump, an ARI certified rating is available
for many combinations.

The AEPT models are equipped with an ECM

TM

 motor.  An

ECM

TM

 motor is more efficient than a standard PSC motor

and offers features such as soft-start, controlled off-delays,
and constant CFM.  Additional features and the associated
controls are  discussed later in this manual.

Electric heat is available for all models. This is an accessory
and is not provided with the equipment.  Use only the
electric heat kits identified in the “Electric Heat” section of
this manual.
These air handlers are intended for use with a room
thermostat.  This thermostat is not supplied with this
equipment. Only thermostats that use 24 VAC operating
voltage can be used.

UNIT INSPECTION

Upon delivery, inspect the unit for damage.  Any damage
must be reported immediately to the carrier.  Do not install
this equipment if it is determined that the integrity or safety
has been compromised by freight damage.

Using the table “Model Identification” section, check the
equipment model number to ensure the unit is appropriately
sized for the condenser unit.

If an incorrect unit is supplied, it must not be installed and
it is to be returned to the supplier.  The manufacturer
assumes no responsibility for the installation of incorrectly
delivered units.

The evaporator coil contains a high-pressure inert gas
holding charge.

ELECTRIC HEAT

WARNING

REFER TO THE “INSTALLING ELECTRIC HEAT” SECTION
OF THIS MANUAL AND THE INSTRUCTIONS PROVIDED
WITH THE HEAT KIT FOR THE CORRECT INSTALLATION
PROCEDURE.

WARNING

THE ELECTRICAL CHARACTERISTICS OF  THE  AIR
HANDLER, THE ELECTRIC HEAT KIT, AND THE SUPPLY
POWER MUST AGREE, UNLESS USING HKR3 (3 PHASE)
SERIES HEAT KIT.  THIS AIR HANDLER DOES NOT HAVE
FACTORY INSTALLED ELECTRIC HEAT.  ELECTRIC
HEAT IS AVAILABLE AS AN ACCESSORY.  IF INSTALLING
THIS OPTION, THE 

ONLY

 HEAT KITS THAT CAN BE USED

ARE THE HKR SERIES AS INDICATED BELOW:  NOTE:
THE AMANA BRAND EHK, ECB, EDB, AND EDK KITS ARE

NOT

  APPROVED FOR USE WITH  THESE  AIR

HANDLERS.

The heating mode temperature rise is dependent upon the
system airflow, the supply voltage, and the heat kit size
(kW) selected. Use 

Tables 1-3 

 to determine the

temperature rise (

o

F).

3

5

6

8

10

15

20

21

600

18

28

35

41

800

13

21

26

31

42

1000

11

17

21

25

34

50

1200

9

14

18

21

28

42

56

62

1400

8

12

15

18

24

36

48

53

1600

7

10

13

15

21

31

42

46

1800

6

9

12

14

19

28

37

41

2000

5

8

11

12

17

25

34

37

HEAT KIT NOMINAL kW

CFM

Table 1

230/1/60 Supply Voltage - Temperature Rise Table °F

3

5

6

8

10

15

20

21

600

17

27

34

39

800

13

20

25

30

40

1000

10

16

20

24

32

48

1200

8

13

17

20

27

40

53

59

1400

7

11

14

17

23

34

46

51

1600

6

10

13

15

20

30

40

44

1800

6

9

11

13

18

27

36

39

2000

5

8

10

12

16

24

32

35

CFM

HEAT KIT NOMINAL kW

Table 2

220/1/60 Supply Voltage - Temperature Rise Table  °F

3

5

6

8

10

15

20

21

600

16

25

32

37

800

12

19

24

38

38

1000

10

15

19

22

30

46

1200

8

13

16

19

25

38

51

56

1400

7

11

14

16

22

33

43

48

1600

6

9

12

14

19

28

38

42

1800

5

8

11

12

17

25

34

37

2000

5

8

10

11

15

23

30

34

CFM

HEAT KIT NOMINAL kW

Table 3

208/1/60 Supply Voltage - Temperature Rise Table °F

Note:  For installations not indicated above the following
formula is to be used:

TR = (kW x 3412) x (Voltage Correction) x 1.08 / CFM

Where: TR

= Temperature Rise

KW

= Heater Kit Actual kW

3412

= Btu per kW

Voltage Correction

=.96 (230 Supply Volts)
=.92 (220 Supply Volts)
=.87 (208 Supply Volts)

1.08

= Constant

CFM

= Measured Airflow

NOTE:  The Temperature Rise Tables can also be used to
determine the air handler airflow delivery.  When using
these tables for this purpose set the room thermostat to

Summary of Contents for AEPT

Page 1: ...Company L P IO 230F 2550 North Loop West Suite 400 Houston Texas 77092 08 04 www goodmanmfg com or www amana hac com 2003 2004 Goodman Manufacturing Company L P INSTALLATION OPERATING INSTRUCTIONS FO...

Page 2: ...092 713 861 2500 IMPORTANT SAFETY INSTRUCTIONS Recognize Safety Symbols Words and Labels The following symbols and labels are used throughout this manual to indicate immediate or potential hazards It...

Page 3: ...area such as a garage utility room or parking area and a carbon monoxide producing device is operated therein there must be adequate direct outside ventilation This ventilation is necessary to avoid t...

Page 4: ...USTAGREE UNLESS USING HKR3 3 PHASE SERIES HEAT KIT THIS AIR HANDLER DOES NOT HAVE FACTORY INSTALLED ELECTRIC HEAT ELECTRIC HEAT ISAVAILABLE AS AN ACCESSORY IF INSTALLING THIS OPTION THE ONLY HEAT KITS...

Page 5: ...OR OBJECTIONABLE FUMES ODORS INTO THE DUCTWORK The return ductwork is to be introduced into the air handler bottom upflow configuration Return Air Filters Each installation must include a return air f...

Page 6: ...e building supply connects to the stripped black and white wires contained in the air handler electrical compartment cavity Aground screw is also contained in this area Attach the supply wires to the...

Page 7: ...NT NOTE In order to prevent damage to the sensing bulb it is not permanently installed in the factory This bulb is to be removed prior to brazing Place in proper location after braze joint has cooled...

Page 8: ...that allows for access to all sides To prevent the evaporator coil pan from sweating the DPI accessory insulation kit is to be used when performing this conversion Note The DPI kit is not supplied wi...

Page 9: ...te The upper drain will become the secondary drain which is mandatory in many municipalities 7 Install the plastic plug removed in step 5 to the right side lower access panel and the oval shaped rubbe...

Page 10: ...n the OFF position For most applications this setting is to be changed according to the electric heat size and the outdoor unit selection The AEPT product uses a General Electric ECMTM motor This moto...

Page 11: ...PT MODELS SEE SUPPLEMENTAL INSTALLATION AND OPERATING INSTRUCTIONS FOR AEPT MODELS ROOM THERMOSTAT W Y G R 18 GA 4 WIRES WITH COOLING 3 WIRES WITHOUT R G W Y TO CONDENSING UNIT 24V CONNECTIONS 18 GA 2...

Page 12: ...UF ARPF ARPT 18 60 ABOVE 10 KW HEAT PUMP B L U E W H I T E C W2 R E D Y O R R Y C O W2 18 GA 7 WIRE R G E R AR UNIT RED OT 1 OT 2 3 EHR 1 2 4 BROWN SEE NOTE 2 NOTES 1 OUTDOOR THERMOSTAT OT 1 SHOULD BE...

Page 13: ...y available Follow the thermostat manufacturer s instruction for installation START UP PROCEDURE Prior to start up ensure that all electrical connections are properly sized and tightened All panels mu...

Reviews: