PM 1000087 000 12
Device handbook SINEAX AM2000
7/91
4. Mechanical mounting
►
The AM2000 is designed for panel mounting
Please ensure that the
are not exceeded when determining the
place of mounting (place of measurement).
By installing, the device becomes part of an electrical power installation that must be
designed, operated and maintained in accordance with country-specific regulations so that
the installation is safe and provides prevention against fire and explosion as far as possible.
It is the task of this installation to ensure that dangerous connections of the device can not
be touched during operation and that the spread of flames, heat and smoke from the interior
is prevented. This may be done by providing an enclosure (e.g. case, cabinet) or using a
room accessible to qualified personal only and compliant with local fire safety standards.
4.1 Panel cutout
Dimensional drawing AM2000:
4.2 Mounting of the device
The device is suitable for panel widths up to 8mm.
a) Slide the device into the cutout from
the outside. Orientation as shown.
b) From the side slide in the mounting
clamps into the intended openings and
pull them back about 2 mm
c) Tighten the fixation screws until the
device is tightly fixed with the panel
4.3 Demounting of the device
The demounting of the device may be performed only if all connected wires are out of service. Remove all
plug-in terminals and all connections of the current and voltage inputs. Pay attention to the fact, that
current transformers must be shorten before removing the current connections to the device. Then
demount the device in the opposite order of mounting (4.2).