Mounting and operating instructions
9.1.3
Safety elements
9.1.4
Feeding
No.
Description
Cause
Elimination
Checking time
Reaction
E20
01
SER Test
SER Test signal unsuccessful
SER short-circuit to the earth.
Check the cabling of the sensor or the
jumper.
Prior to closing
A
02
SER too slow
SER reacts too slowly.
Check the cabling of the sensor.
Check for polarity reversal/test signal.
E21
01
SES Test
SES Test signal unsuccessful
SES short-circuit to the earth.
Check the cabling of the sensor or the
jumper.
Prior to opening
A
02
SES too slow
SES reacts too slowly.
Check the cabling of the sensor.
Check for polarity reversal/test signal.
E22
01
EMY Test
EMY input on 24 V
Check the jumper EMY.
Check the cabling EMY.
Permanent
H
02
Malfunction EMY input
A
No.
Description
Cause
Elimination
Checking time
Reaction
E30
01
30 V Error
30 V too low
Mains failure, overload motor. Check the feed-in.
Replace the hardware.
Permanent
A
02
30 V too high
03
Error upon switching-on
E31
01
24 V General
Error upon switching-on
Overload, short-circuit 24 VDC onto terminals
X101, X102 or X116 (Fire protection PCB/Relay
PCB)
Permanent
A
Restart after 10 s
02
Over- resp. under-voltage
E32
01
24 V Safety
Over- resp. under-voltage
Overload, short-circuit 24 VDC onto terminals
X105 or X107
E33
01
24 V E-Lock
Error:
Over- resp. under-voltage
Overload, short-circuit 24 VDC onto terminal X108
02
Premonition:
Over- resp. under-voltage
E34
01
24 V CAN
Over- resp. under-voltage
Overload, short-circuit external power supply CAN
9.1.6
Options
9.1.5
System
9.1.7
Closing sequence / Interlock function
No.
Description
Cause
Elimination
Checking time
Reaction
E50
01...99
System error
Unexpected hard
-
ware or software
event
Switch the drive mechanism off/on.
Carry out a Factory Reset, carry out a Software Update,
inform the manufacturer.
Permanent
W or H or F
E51
01...99
E52
01...99
No.
Description
Cause
Elimination
Checking time
Reaction
E60
00
Relay PCB 0
Option PCB has been remo
-
ved, its address changed or
become defective
Check if the option is provided.
If defective: Replace or remove from the configu
-
ration.
Note:
Deleting of error 60
see chapter 13.6.1
Permanent
W
10
Relay PCB 1
Permanent
W
20
Relay PCB
Permanent
W
30
Fire-protection PCB
Permanent
A
No.
Description
Cause
Elimination
Checking time
Reaction
E70 xx CAN bus setting
CAN address xx existing
twice
Correctly define the role of the closing sequence or the
interlock function
Permanent
W
E71
01
CAN connection
No CAN connection
Plug in, check or replace the CAN cable.
Check if all the CAN participants are switched on.
Permanent
W
Summary of Contents for SD-L F 9365 Series
Page 88: ......
Page 89: ......
Page 90: ......
Page 91: ......
Page 92: ......
Page 93: ......
Page 94: ......
Page 95: ......
Page 96: ......
Page 97: ......
Page 98: ......
Page 99: ......
Page 100: ......
Page 101: ......
Page 102: ......
Page 103: ......
Page 104: ......
Page 105: ......
Page 106: ......
Page 107: ......
Page 108: ......
Page 109: ......
Page 110: ......
Page 111: ......
Page 112: ......